702288
2
Zoom out
Zoom in
Vorherige Seite
1/20
Nächste Seite
2
7. (Optional) Connect the open collector output to an external
signalling device or panel to have an independent fault
supervisory.
8. Connect the flat cable between the control panel (connector
J20) and the ATS7300 (connector CON1or CON2).
9. Connect the antenna to the GSM module
10. Insert the SIM module into the SIM socket (CON5).
11. Apply power to the control panel and the GSM module.
12. Check the field strength (FS LED). When required, move the
antenna in order to get the best signal.
DESCRIPTION OF THE ATS7300 (REF. TO FIGURE )
No. Description Function
1
GSM module Sony Ericsson GM47 GSM
module. Includes antenna
connection (MMCX
connector)
CON5 SIM socket. Holds GSM SIM
card.
CON3 Feature connector. Only for
factory use.
F1, Automatic fuse Used to protect the GSM
module against
shorts/reversed connections
on the battery input.
CON 1, BATT IN + Battery + connection
CON 1, BATT IN - Battery – connection
CON 1 NC Not connected
CON 1 OC Open collector (see fault
indicator output description
below).
CON 2/CON 4
(System connector)
Communicates between the
ATS7300 and the main
panel.
LEDs LED’s indicating status.
FAULT INDICATOR OUTPUT (REF. TO FIG. CON1 SYMBOL )
OC
Open collector state:
The open collector is controlled by the state of the battery fuse
(F1), presence of the battery and the presence of the GSM
network.
The open collector is low (active) if the battery is present, the
battery fuse is ok and the GSM network is detected.
This low state can sink current and is compared to + 12V. In case
of any error condition the output is high.
IMPORTANT:
After power up the open collector is always high for some time, this
is because the ATS7300 has not yet detected the GSM network.
The open collector has the same functionality as the line fault,
which is reported to the panel, except that the open collector is not
delayed.
Line fault reported to the panel is delayed with 1 minute.
LED'S
MI
The MI LED (green) displays the status of the communication
interface to the panel.
Table 1. MI LED status
LED Description
Duty
cycle
Rate
(+/- 10%)
100% - Power ON (in case none of the
cases below are valid)
0% - No Power or Power Failure
25% 1 sec Initialisation OK, waiting for
communication
50% 1 sec Everything OK, communication
running
75% 500 ms Hardware failure
50% 250 ms Failure in communication, waiting for
re-initialisation.
CS
The CS LED (Red) indicates status of the audio information
transmitted to the central station
Table 2. CS LED status
LED Description
Duty
cycle
Rate
(+/- 10%)
100% - Connected
0% - Off line
10% 1 sec Connecting
50% 1 sec Ringing present
FS
The FS LED (green) indicates the field strength or signal strength
found by the GSM module. The number of flashes indicates the
level. Between each set of flashes a pause of 1 second is inserted.
Table 3. FS LED status
LED Description
Off No field strength (no network
detected)
Blink (1 – 5) Field strength indication from poor
(1) to excellent (5)
On Power on, not connected to a
network
GSM
The GSM LED (green) indicates the status of the GSM module.
Table 4. GSM LED status
LED Description
Off No power or the module is in the off
state
Blink Power on, connected to a network
On Power on, not connected to a
network
The GSM module will signal a line fault to the control panel if the
GSM module does not detect the home network for 1 minute.
.Technical Specifications
Power supply
Via ribbon cable from control panel
Via CON1, BAT from backup battery
10 – 15 V
10 – 15 V
Current Consumption (at 13.8 V ± 5%)
MI Bus
GSM Offline
GSM Online
GSM Online Peak
20 mA
15 mA
110 mA
2A
Open collector output current (CON13, OC)
15 mA max. at 13.8 V.
2

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Aritech ATS7300 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info