SET
SET
C.s.lo.= Control set point lower limit.(for
selected output)
Adjustable between 0 and C.s.Hi.
C.s.Hi.= Control setpoint upper limit.(for
selected output)
Adjustable between C.s.Lo. and Upper scale
value.
a2.s .l= Alarm2 set value lower limi t.
Adjustable between 0 and A2.S.H
parameter value.
a2.s.H= Alarm2 set value upper limit.
Adjustable between A2.S.L
parameter value and upper scale
value.
a2.Hy = Hysteresis of the Alarm2
output.
Adjustable between 1 and 50 °C.
A2.st. = The state of Alarm2 output.
Hi = If A2 output is above the set
value. (on)
lo = If A2 output is above the set
value (off).
A2.Er. = State of Alarm2 output in the
case of sensor failure.
on = A2 output is probe failure (on).
off= A2 output is probe failure (off).
A2. tp = Function of Alarm2 type.
Four kinds of functions can be
selected.
ind E. = Independd nt alarm
(Indep endent)
dE. = Deviation
bAn d = Band alarm (Band)
bAn .i = Band with inhibitio n
inp.t. = Input type selection.
Pt.0 = PT100 Decimal,
Pt = PT100,
FE.cn.= J type,
nc.nA.= K type,
c.cn. = T type,
p10.r .= S type,
P13.r .= R type thermocouple selection.
This parameter varies when changing
some parameters.
Unit = The temperature unit.
°C = °C, °F = °F
(This parameter varies when
changing some parameters.)
C.o.sE = Control output selection
C-A2 = C/A2 (Relay) output selection
SSR = SSR output selection
F .kE.C. = Function key setting parameter
nonE = Function key is off.
C2.S.A. = The function key with 2.set value is used.
manu. = Manual mode can be achieved with the function key .
dSP .o. = Only the temperature display mode is entered with
function key .
C. Pb = Proportional band.(for selected
output)
Adjustable between %0 .0 and %100 .0.
C. Pb = %0 .0,On-Off control is selected.
C. ti = Integral time.(for selected output)
Adjustable between 0 and 100.0 minutes.
C. ti = 0.0,integral impact is disable.
parameter is different from “0”,this
parameter appears.
C. Pb
C.Hys = Hysteresis of the output.(for
selected output)
Adjustable between 1 and 50 °C.
= 0,this parameter is active.C. Pb
C. td = Derivative time.(for selected output)
Asjustable between 0.00 and 25.00 minutes.
C. td = 0.0, derivative time is disabled.
parameter is different from”0”,this
parameter appears.
C. Pb
C. Ct. = Period time.(for selected output)
Adjustable between 1 and 250 second.
parameter is different is different
from“0”,this parameter appears.
C. Pb
C.p.st = The ratio of output power at the
setpoint.Adjustable between %0 and %100.
C.E.P .s. = The percentage of faulty sensor
selected output power .
Adjustable between %0 and %100.
C.typ. = Control output type
C.typ. = HEAt means heating control.
C.typ . = CooL means cooling control.
While the parameter names appear , if and
keys are pressed together , returns to the program mode.
S.Cod = Security menu access
code.
It should be 201 1.
Cosc. = Parameters of CoN.o.
menu security access level code.
nonE = Invisible.
P .yEs = Modification can be done.
P . no = Only visible.
m.SEt. = The percentage of manual output parameter .
Adjustable between %0 and %100.
This parameter allows manual adjustment of the output
power when the manual output selection.
C. Pb.= 0, this parameter is not seen.
If co.SE parameter is different
from C-A2, this parameter is seen.
a.2.sc. = Parameters of al2.o.
menu security access level code.
nonE = Invisible.
P .yEs = Modification can be done.
P . no = Only visible.
Co.sc. = Parameters of Conf.
menu security access level code.
nonE = Invisible.
P .yEs = Modification can be done.
P . no = Only visible.
S.t.Sc. = Parameters of S.tun.
menu security access level code.
nonE = Invisible.
P .yEs = Modification can be done.
Co.sc. = Parameters of Conf.
menu security access level code.
no = Parameter settings are not
change.
yEs = Parameter setting will be
restored.
2/4
C.s.Lo.
C.s.Hi.
C. pb
C. ti
C. td
C.p.st
C.Hys
C. Ct.
C.typ
s.s.t.s.
C.E.p.s.
Con.o.
AL2.o.
ConF .
S.tun.
SEcu.
S.Cod.
Co.sc.
m.SEt.
a.2.sc.
Cn.sc.
S.t.sc.
dEF .P .
inp.t.
Unit
fltr .
C.o.sE
offs.
s.t.Co.
F .k.E.C.
A2.S.L
A2.S.H
A2.HY
A2.tP
A2.St.
A2.Er .
SET
SET
SET
SET
SET
F
Programming mode
This parameter indicates the time to reach set point
value when the device is first ener gised.
Adjustable between 0 and 250 minutes.
If 0 is selected, soft start feature will be enable and the
device reaches set point value quickly .
Setting Pb = 0, soft start feature will be disabled .
Sst.S =Sofy starter timer set value
fLtr. = Coefficient of digital filter .
Filter for display value.
Adjustable between 1 and 200 . If this parameter is 1,
digital filter runs most quick. If the parameter is 200 ,
the filter run most slow. The value of parameter should
be increased in interference.
oFfS. =
Offset value is added to the measurement value.
Adjusted between -100 and +100°C.The normal value is 0.
Offset value.
St.Cu = Self tune control parameter .
If both keys are pressed ,yEs
message is displayed on the screen
and selftune process is started
automatically .
If both keys are pressed, no
message is displayed on the screen
and selftune process is stopped.
SET
If key is pressed while holding key , the programming mode is enabled.
SET
F
Entering from the programming mode to the run mode:
If no key is pressed within 20 seconds during programming mode, the data is stored automatically and the run mode is entered.
Alternatively , the same function occurs first pressing key and key is pressing programming mode is entered.Then and keys are pressing
together , data is recorded and running mode is entered.
Modification Of Parameter Diagram
When holding key , the value of parameter flashes and using
keys the requested value can be adjusted.
If key is pressed and held 0.6 seconds, the value of the selected
parameter changes rapidly . If waited enough,the value increases 100 at each
step. After 1 second following the release of the key , initial condition is
returned.The same procedure is valid for the decrement key .
Chys
6
5
6
SET
SET SET
SET
C.s.lO.
inp.t.
A2.s.l
Co.sc.
C1.sE.
C.s.Hi.
Unit
A2.s.H
A2.Sc.
C2.SE.
C. PB
Fltr .
A2Hy .
Cn.Sc.
A2.SE.
C.HyS
C.o.SE.
A2.tp
S.t.Sc.
C. ti
offs.
a2.st.
dEf.P .
C. td
f.k.E.C.
a2.Er .
a2.Er .
C. Ct.
m.sEt.
C.P .St.
C.EP .S.
S.s.t.S.
C.typ.
TC input
TC input
TC input
TC input
TC input
PT100 input
PT100 input
PT100 input
PT100 input
PT100 input
0
FE.cn.
0
0
25
2
2
C-A2
indE
P .yEs
P .yEs
400
P .yEs
400
P .yEs
500
4.0
0
Hi
no
1.00
nonE
on
no
20
50
0
0
0
HEat
-200
Pt.
-200
600
°C
600
DEF AULT P ARAMETERS
Set parameters
Control output
parameters
Alarm2 output
parameters
Configuration
parameters
Self tune
parameters
Security
parameters
SET
SET
ET201 1-E-06-201408
When the self tune begins,
PIdt. message
and measurement value are shown
alternately .
After the completion of the self tune process,
st.Co. parameter is automatically changed to
no and the device returns to working mode.
If the measured temperature is higher than
90% of the set value at the beginning of the
self tune process, then tE.Hi. message is
shown alternately and the measured
temperature is waited to go below %60 of
the set value. After that, self tune operation
is started automatically .
If it is intended to abort the self tune
process, St.Co. parameter is changed to
no and key is pressed.