_______________________________________________________________________________________________________________________________________________________BA GS1000pro hugomüller; DE,GB - 23358- 2014.05-V01
INSTRUCTION MANUAL ROOM CLIMATE CONTROL DEVICE GS10.00PRO
SAFETY INSTRUCTIONS AND BASICS
Technical data / Connection diagram
Safety instructions
Power supply:
Connect as stated on the product!
CAUTION! DANGER OF LIFE / RISK OF FIRE AND ELECTRIC SHOCK!
!!!Installation and assembly of electrical equipment must be carried out only by a skilled person!!!
!!!For devices with 24V ACDC
supply voltage following applies:
SELV
Channels (potential-free):
4 switching channels, normally open
Connect the supply voltage/frequency as stated on the product!
Disconnect device from power supply for wiring and installation purposes! Check power supply is disconnected!
After completing the installation the terminal cover MUST be reattached! The device may only be operated with front and terminal cover!
The safety precautions of DIN VDE 0100, electric shock, and fire danger have to be met.
Defective devices / sensors have to be put out of service immediately!
For devices with 24V ACDC supply voltage following applies: The supply voltage must meet the requirements for SELV!
Installation and assembly of electrical equipment must be in accordance with local building and electrical codes!
Warranty void if housing opened by unauthorised person!
Do not use the sensor for safety-relevant gas measurements!
Switching capacity:
Connect as stated on the product!
Analogue control outputs:
3 x 0-10 Volt
Permitted ambient temperature:
0°…+50°C
Housing:
self-extinguishing thermoplastic
Mounting:
wall mounting
Type of connection:
Screw terminals
Type of protection:
IP 20 to DIN EN 60529
Class of protection:
II when installed according to regulations
Features of actions:
1B
Usage / disposal
The climate control device is provided for use in interior and living areas!
The device includes sensors for measuring and controlling CO
2
concentration, relative humidity and temperature.
The relay switches in according to the set threshold values for CO
2
and relative humidity (example for application: ventilation). Via
analogue control outputs the measured values of the CO
2
concentration, relative humidity and temperature can be output.
The device is to be disposed in an environment-friendly way and according to current law.
ASSEMBLY
Assembly
Disconnect device from power supply for wiring and installation
purposes! Check power supply is disconnected!
Attention! You have to check and consider the safety instructions above!
This device is suitable for wall mounting or for mounting on a flush-mounting box.
The device should not be exposed to air draught or direct sunlight.
Don´t install it curtains, or in niches, or close to heat sources.
The device should not be exposed to dusty environment.
Ensure that no dust get inside of this device.
For devices with 24V ACDC supply voltage following applies:
The supply voltage must meet the requirements for SELV!
After initial startup, the device requires up to 5 minutes until the first correct
measurement is possible
Installation note: For an easy mounting and installation you can unplug the ribbon cable to remove the front cover completely. (Ribbon cable: logic cable connection
between front-cover and back-cover). After mounting / installation => For a proper function of the device you have to reconnect in the ribbon cable.
STEP 1: Open the device at the bottom and remove the front cover!
STEP 2: Remove the terminal cover (shown in grey)!
STEP 3: Mount the rear cover to the wall or on a flush-mounting box(consider STEP 4)!
STEP 4: Feed the cables through the appropriate cable passages:
Cable passage I: Cables for analogue outputs and GND (Terminal 1,2,3,4)
Cable passage II: Cables for Relay A and Relay B (Terminal 5,6 / 7,8)
Cable passage III: Cables for Relay C and Relay d (Terminal 9,10 / 11,12)
Cable passage IV: Cables of the supply voltage (Terminal 13,14,15)
STEP 5: After completing the installation the terminal cover MUST be reattached!
STEP 6: Reattach the front cover!
OPERATION
Settings and functions
Functions
(examine)
Relay Sensors
Threshold
settings
Setting range
(thresholds)
Response to the set thresholds Permanent switching
Factory
setting
CO
2
concentration
Relay
A
CO
2
[ppm]
Via
Rotary switch
A
700ppm -
1.300ppm
(± 100 ppm)
The relay switches on when exceeding
the threshold
(Hysteresis ± 50 ppm)
Turn rotary switch to left end of scale (Pos. MIN): PERM ON
Turn rotary switch to right end of scale (Pos. MAX): PERM OFF
1.000ppm
CO
2
concentration
Relay
B
CO
2
[ppm] No settings possible!
Fix threshold 1400 ppm!
The relay switches on when exceeding
1400 ppm
(Hysteresis ± 50 ppm)
No settings possible!
Humidify
Relay
C
RH [%]
Via
Rotary switch
C
15%RH - 45%RH
(± 3%)
The relay switches on when exceeding
the threshold
(Hysteresis ± 3%)
Turn rotary switch to left end of scale (Pos. MIN): PERM ON
Turn rotary switch to right end of scale (Pos. MAX): PERM OFF
PERM
OFF
Dehumidify
Relay
D
RH [%]
Via
Rotary switch
D
50%RH - 80%RH
(± 3%)
The relay switches on when exceeding
the threshold
(Hysteresis ± 3%)
Turn rotary switch to left end of scale (Pos. MIN): PERM OFF
Turn rotary switch to right end of scale (Pos. MAX): PERM ON
65%RH
LED-displayRelay status
LED-DISPLAY
OFF
LED- DISPLAY
PERMANENT GREEN
LED- DISPLAY
FLASHING GREEN
LED- DISPLAY
PERMANENT ORANGE
CO
2
-LED
Relay A „OFF
Relay B „OFF
Relay A „OFF
Relay B „OFF
Relay A „ON Relay A and/or Relay B „ON
Permanent OFF setting via rotary switch
(setting via rotary switch A)
Measured value is below threshold
(setting via rotary switch A)
Measured value is above threshold
(setting via rotary switch A)
Measured value over 1400 ppm or
Permanent ON setting via rotary switch
(setting via rotary switch A)
CO
2
concentration OK
CO
2
concentration above threshold
CO
2
concentration poor
RH-LED
Relay C „OFF
Relay D „OFF
Relay C „OFF
Relay D „OFF
Relay C and/or Relay D „ON
Permanent OFF setting via rotary switch
(setting via rotary switch C or D)
Measured value is below threshold value for dehumidifying
and/or above threshold for humidifying
(setting via rotary switch C or D)
Measured value is above threshold for dehumidifying
and/or below threshold for humidifying or
Permanent ON setting via rotary switch
(setting via rotary switch C or D)
Relative humidity below threshold
Relative humidity above threshold
Analogue control outputs
Hugo Müller GmbH & Co KG
Sturmbühlstraße 145-
149
D-78054 VS-
Schwenningen
Tel.: +49 (0) 7720 80 836
Fax: +49 (0) 7720 31 083
E-Mail: info@hugo-mueller.de
Internet: www.hugo-mueller.de
Analogue control output
Measuring range of the output
Value output
CO
2
0 10 Volt output
0 2000ppm
0 Volt = 500ppm
10 Volt = 2000ppm
Relative humidity
0 10 Volt output
15 85%RH
0 Volt = 15%RH
10 Volt = 85%RH
Temperature
0 10 Volt output
0 50°C
0 Volt = 0°C
10 Volt = 50°C
2

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Hugo Muller GS10.00PRO wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info