T600HCx-3 Single-Stage Thermostats Installation Instructions 5
Configuring the T600HCx-3 Thermostat
The T600HCx-3 thermostat comes from the factory
with default settings for all configurable parameters.
The default settings are shown in Table 2. To
reconfigure the parameters via the thermostat, follow
the steps in this section.
1. To access the Installer Configuration Menu, press
and hold the MENU key for approximately 8
seconds.
2. Once the Installer Configuration Menu begins,
press the NO key to scroll through the parameters
listed in Table 2.
3. When the desired parameter is displayed, use the
YES key to choose the desired selection option.
4. Press the YES key and then the NO key to
continue scrolling through the parameters.
To exit the Installer Configuration Menu any time, press
the MENU key, and at the exit prompt, press the YES
key. To pass over a parameter without changing it,
press the NO key.
When the thermostat is in the Installer Configuration
Menu and left unattended for approximately 8 seconds,
the thermostat reverts to the Status Display Menu.
Configuring Inputs DI1 and DI2
When DI1 and DI2 are configured for an alarm
condition, an alarm condition is displayed locally when
the input is closed. An alarm message is included on
the scrolling Status Display Menu and when the
message is displayed, the backlight momentarily
lights up.
Each input can be configured to the Selection Options
included in Table 2.
Table 2: Installer Configuration Menu (Part 1 of 4)
Parameter
Appearing
on Display
Description and Default Selection Options
DI1
1
Configuration of Digital Input 1.
Default: None
(None): No function is associated with an input.
(Service): A Service alarm is displayed on the thermostat when the
input is energized. This input can be tied into the air conditioning unit
control card, which provides an alarm should there be a malfunction.
(Filter): A Filter alarm is displayed. This alarm can be connected to
a differential pressure switch that monitors a filter.
(RemOVR): Temporary occupancy request via a remote input. This
override function is controlled by a manual remote occupancy
override. When enabled, this condition disables the override
capability of the thermostat.
(RemNSB): Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact.
Contact open = Occupied; contact closed = Unoccupied.
DI2
1
Configuration of Digital Input 2.
Default: None
(None): No function is associated with an input.
(Service): A Service alarm is displayed on the thermostat when the
input is energized. This input can be tied into the air conditioning unit
control card, which provides an alarm should there be a malfunction.
(Filter): A Filter alarm is displayed. This alarm can be connected to
a differential pressure switch that monitors a filter.
(RemOVR): Temporary occupancy request via a remote input. This
override function is controlled by a manual remote occupancy
override. When enabled, this condition disables the override
capability of the thermostat.
(RemNSB): Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact.
Contact open = Occupied; contact closed = Unoccupied.
5

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Johnson Control T600HCP-3 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info