INSTALLER’S SETTING OPTIONS
● Press and hold ‘wireless remote controller signal receiver part’ of the remote controller for 3
seconds or longer to enter the installer function.
● Select "02" for Code value.
- You may need to press ‘▲’, ‘▼’ button to change the code value.
● At the Value 1 and Value 2 fields, press the use ‘▲’, ‘▼’ button to select group address and in-
door unit address value, and press ‘Done’ button to complete the address setting.
- If you do not press ‘Done’ button, your value settings will not be applied.
- Hexadecimal values, can be set from 0~F.
h If no buttons are pressed for about 60 seconds after the setting, it automatically exits from the
setting mode.
h Address setting
- Value 1: group number
- Value 2: indoor number
Central control address (air conditioner /General, DX type ventilator)
This function allows the user to set the central control address of the indoor units during the cen-
tral controller connection.
INSTALLER’S SETTING OPTIONS
● Press and hold ‘wireless remote controller signal receiver part’ of the remote controller for 3
seconds or longer to enter the installer function.
● In the Code input field, select test run code value ‘01’.
- You can press ‘▲’, ‘▼’ button to change the code value.
● At the Value 1 field, press the ‘▲’, ‘▼’ button to select the test run mode, and press ‘Done’
button to start the test run.
- If you do not press ‘Done’ button, the setting value will not be applied.
● During the test operation, if you operate any of the following functions, the test run will be in-
terrupted and stop.
- Operation mode, temperature up/down, fan speed, Air flow direction, power on/off button.
Test Run Operation (air conditioner / DX type ventilator)
Test Run (air conditioner / DX(Direct Expenditure) type ventilator)
You must perform test operation after the product installation.
For details related to the trial operation, refer to the product manual.
h Test operation mode value
- 01: cooling operation
- 02: heating operation