OWNER’S & INSTALLATION
MANUAL
AIR CONDITIONER
Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
Please retain this installation manual for future reference after reading it thoroughly..
WIRED REMOTE CONTROLLER
PREMTB100, PREMTBB10, CREMTB100
Copyright © 2016 - 2018 LG Electronics Inc. All Rights Reserved.
MFL69312302
Rev.09_111918
ENGLISH
FRANÇAIS
ITALIANO DEUTSCH ESPAÑOL
РУССКИЙ ЯЗЫК
POLSKI
PORTUGUÊS
中文
ČEŠTINA
1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 1000
1

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Inhalt der Seiten


  • Page 1

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 1000

    ENGLISH
    FRANÇAIS
    ITALIANO
    DEUTSCH

    OWNER’S & INSTALLATION
    MANUAL

    ESPAÑOL

    AIR CONDITIONER

    РУССКИЙ ЯЗЫК
    POLSKI
    PORTUGUÊS

    Please read this installation manual completely before installing the product.
    Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
    Please retain this installation manual for future reference after reading it thoroughly..

    中文

    WIRED REMOTE CONTROLLER
    PREMTB100, PREMTBB10, CREMTB100

    ČEŠTINA

    MFL69312302
    Rev.09_111918

    www.lg.com
    Copyright © 2016 - 2018 LG Electronics Inc. All Rights Reserved.



  • Page 2

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 2

    TIPS FOR SAVING ENERGY

    2

    IMPORTANT SAFETY INSTRUCTIONS

    IMPORTANT SAFETY INSTRUCTIONS

    Here are some tips that will help you minimize the power consumption when you use the air
    conditioner. You can use your air conditioner more efficiently by referring to the instructions
    below:

    READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.








    Do not cool excessively indoors. This may consume more electricity.
    Block sunlight with blinds or curtains while you are operating the air conditioner.
    Keep doors or windows closed tightly while you are operating the air conditioner.
    Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
    Speed up the fan to cool or warm indoor air quickly, in a short period of time.
    Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the
    air flow or reduce the cooling / dehumidifying functions.

    Always comply with the following precautions to avoid dangerous situations and ensure peak
    performance of your product

    ! WARNING
    This symbol indicates potentially hazardous situation which, if not avoided could result in death or
    serious injury.

    ! CAUTION
    This symbol indicates a potentially hazardous situation which, if not avoided, may result in minor
    or moderate injury.

    ! WARNING
    Installation
    • For electrical work, contact the dealer, seller, a qualified electrician, or an authorized service Center.
    - Do not disassemble or repair the product. There is risk of fire, electric shock, explosion, equipment
    malfunction, or injury.
    • Request to the service center or installation specialty store when reinstalling the installed product.
    - There is risk of fire, electric shock, explosion, equipment malfunction, or injury.
    • Do not disassemble, fix, and modify products randomly.
    - There is risk of fire, electric shock, explosion, equipment malfunction, or injury.
    • The product shall be installed according to the national standards and local code.
    • Apply totally enclosed noncombustible conduit in case of local building code requiring plenum.
    • Use appropriate unit mounting procedures.
    • Avoid direct sunlight.
    • Avoid moist areas.

    In-Use
    • Do not place flammable objects close to the product.
    - There is risk of fire, electric shock, explosion, equipment malfunction or injury.

    For your records
    Staple your receipt to this page in case you need it to prove the date of purchase or for warranty
    purposes. Write the model number and the serial number here:
    Model number :
    Serial number :
    You can find them on a label on the side of each unit.

    • Do not allow product to get wet.
    - There is risk of fire, electric shock, explosion, equipment malfunction or injury.
    • Avoid dropping the product.
    - There is risk of fire, electric shock, explosion, equipment malfunction or injury.
    • If product gets wet, contact your dealer or authorized service center.
    - There is risk of fire, electric shock, explosion, equipment malfunction, or injury. If the instructions
    are not followed, it may cause death or severe injury of the user.
    • Do not use sharp or pointed objects on product.
    - There is risk of fire, electric shock, explosion, equipment malfunction or injury.

    Dealer’s name :
    Date of purchase :

    • Do not touch or pull the lead wire with wet hands.
    - There is risk of product breakdown or electric shock.

    ENGLISH

    TIPS FOR SAVING ENERGY

    3



  • Page 3

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 4

    4

    IMPORTANT SAFETY INSTRUCTIONS

    • Do not clean using powerful detergents like solvent but use soft cloths.
    There is risk of fire, electric shock, explosion, equipment malfunction or deformation.
    • Do not press the screen using powerful pressure.
    There is risk of product break-down or malfunction.

    5
    ENGLISH

    ! CAUTION
    In-use

    TABLE OF CONTENTS

    TABLE OF CONTENTS
    2
    3
    8
    9
    9

    TIPS FOR SAVING ENERGY
    IMPORTANT SAFETY INSTRUCTIONS
    DESCRIPTION
    READ BEFORE OPERATING
    THE CONTROLLER
    Menu Structure

    14 DESCRIPTION OF THE OPERATION
    14
    14
    15
    15
    16
    17
    17

    Main screen
    Menu screen
    Setting screen
    Popup screen
    Monitoring / Sub function screen
    Interface screen
    Returning to the screen

    18 OPERATION SETTING
    18
    18
    19
    20
    21
    22
    23
    24
    25
    25

    On / Off
    Operation mode
    Cooling Operation
    Heating Operation
    Dry Operation
    Fan Only Operation
    AI / Auto operation
    Dual setpoint auto operation
    Power Cool Operation
    Power Heat Operation

    26 OPERATION SETTING VENTILATOR
    26

    Operation mode

    27 TEMPERATURE SETTING
    27
    28

    Controlling Desired Temperature
    Check Room Temperature

    29 WIND SETTING
    29
    29
    29

    Fan speed control
    Fan speed control - ventilation
    Air flow control

    30 HOME LEAVE SETTING
    30

    Home leave (Unoccupied Mode)

    31 HOLD SETTING
    31

    Hold

    32 ADDITIONAL OPERATION –
    VENTILATION
    32

    Additional operation

    33 EXTERNAL EQUIPMENT
    CONTROL SETTING
    33

    External equipment control

    34 PLASMA PURIFICATION
    SETTING
    34

    Plasma Purification

    35 OVERRIDE CONTROL SETTING
    35

    Override control

    36 MONITORING SCREEN
    36
    37

    How to enter fine dust status screen
    Fine dusts status

    38 SUB FUNCTION SETTING
    38
    39
    40
    41
    42
    43
    44
    45
    46

    Sub function entrance and setting method
    Energy Saving Setting
    Plasma Purification Setting
    Fan Auto Setting
    Humidification setting
    Electric Heater Setting
    Robot Cleaning Setting
    Ventilation kit Setting
    Comfort Cooling Setting

    47 ZONE CONTROL SETTING
    47

    Zone Control

    48 LOCK SETTING
    48
    48

    How to enter lock setting
    Lock setting – all, on/off, mode, temperature range lock

    49 TIMER SETTING



  • Page 4

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 6

    6

    Timer entrance and setting method
    Simple timer
    Sleep timer
    Turn-off Reservation
    Turn-on Reservation

    54 SCHEDULE SETTING
    54
    55
    56
    57
    58

    How to enter schedule
    Daily Schedule
    Schedules & Edit
    Schedules & Edit – Add schedule
    Exception day

    59 ENERGY (air conditioner /
    DX ventilator)
    59
    60
    61
    63
    64
    65
    66
    67
    68
    69
    70

    How to enter energy
    Instantaneous power check
    Energy consumption
    Energy saving - Temperature Setback Timer
    Energy saving - Time Limit Control
    Energy setting - outdoor unit capacity setting
    Energy setting - target instantaneous power
    setting
    Energy setting - target power consumption
    Energy setting - target operation time
    Energy setting - Alarm Popup Setting
    Energy setting – Usage data initialization

    71 FUNCTION SETTING
    71
    72
    73
    74
    75
    75
    76
    77
    78
    79
    80
    81
    82
    83
    83

    How to enter function setting
    Function Setting
    Vane angle control setting
    Elevation grill setting
    Robot cleaning setting
    Auto dry setting
    Filter sign check and initialization
    Change temperature setting
    Dead Band
    Wi-Fi pairing setting
    Zone Name setting
    Override Set Time Setting
    Home Leave Set Temperature Setting
    Comfort cooling setting
    ODU Refrigerant Noise Reduction setting

    TABLE OF CONTENTS

    84
    85
    86
    87
    88
    89
    90
    92
    92

    Defrost mode setting
    Smart load control(SLC) setting
    Low noise mode time setting
    Advanced fan speed “Auto” setting
    Delay time (exclusive for ventilation)
    Midnight air cooling (ventilation interface)
    Human detection mode setting
    Discharge direction
    CO2 Fan Control(general ventilator)

    93 USER SETTING
    93
    93
    94
    95
    96
    97
    97
    98
    98
    99
    100
    101
    102
    103
    104
    105
    106
    107
    108

    How to enter user setting
    User Setting
    Language setting
    Setpoint Type Setting
    Temperature unit setting
    Screen saver timer setting
    LCD brightness in idle setting
    External device setting
    External device use
    External device types
    On condition / Off condition
    Date setting
    Time setting
    Summer time setting
    Password setting
    Schedule initialization
    Theme setting
    Humidity display
    System restart

    109 SERVICE SETTING
    109
    109
    110
    111
    112
    113
    114

    How to enter service setting
    Service setting
    Service contact
    Model information
    RMC Version Information
    Error history
    Open source license

    115 INSTALLATION
    115
    117

    Installation of Remote Controller
    Group control

    119 INSTALLATION METHOD
    TO USE EXTERNAL DEVICE
    119

    Cable connection method to use external
    device

    120 AIR CONDITIONER AND
    VENTILATION INTERFACE
    121 INSTALLER SETTING
    121
    122
    124
    125
    126
    127
    128
    129
    130
    131
    132
    133
    134
    135
    135
    136
    137
    138
    139
    140
    141
    142
    143
    144
    145

    How to enter installer setting
    Installer setting – air conditioner
    Installer setting - ventilator
    Test run setting (air conditioner / DX ventilator)
    Central control address setting (air conditioner / general, DX ventilator)
    ESP setting (air conditioner / general, DX
    ventilator)
    Temperature sensor(2TH) setting (air conditioner / DX ventilator)
    Ceiling height setting (air conditioner)
    Static pressure setting(air conditioner)
    Remote controller master / slave setting (air
    conditioner / General, DX ventilator)
    Override Master/Slave setting (air conditioner / General, DX ventilator)
    Dry contact mode setting (air conditioner /
    DX ventilator)
    Fixed air volume (air conditioner / DX ventilator)
    Zone Type Setting(air conditioner)
    Zone Number Setting(air conditioner)
    Emergency heater setting (air conditioner)
    Function control during group Control setting (air conditioner)
    External devices of indoor unit setting (air
    conditioner)
    Expand of Temperature Range (air conditioner)
    Indoor unit address verification (air conditioner / DX ventilator)
    Static pressure step setting (air conditioner)
    Guard timer(air conditioner)
    Fan speed in Cooling thermal off (air conditioner)
    Primary heater setting(air conditioner)
    Air conditioner Fan operation interlocked

    146
    147
    148
    149
    150
    151
    152
    153
    154
    155
    157
    158
    158
    159
    160
    161
    162
    163
    164
    164

    with ventilation setting (air conditioner)
    Indoor unit Auto-Start setting (air conditioner / DX ventilator)
    Occupancy duration time setting(air conditioner)
    CN_CC setting (air conditioner)
    CN_EXT setting (air conditioner / DX ventilator)
    Outdoor unit function master setting (air
    conditioner / DX ventilator)
    Fan continuous operation setting (air conditioner)
    Low Noise Mode Priority setting (air conditioner / DX ventilator)
    Human detection sensor (air conditioner)
    Humidity sensing position (air conditioner)
    ODU cycle priority (air conditioner)
    Outdoor temp. for heating stages (air conditioner)
    Estimated energy display (air conditioner)
    CN_PTC setting (air conditioner)
    Password initialization (air conditioner / general, DX ventilator)
    Product direction (general ventilator)
    Express ventilation priority (general , DX
    ventilator)
    Humidification of stand-alone ventilation
    mode (general , DX ventilator)
    Humidification of ventilation with heating
    operation (DX ventilator)
    Ventilation Fan Speed Alignment (general
    ventilator)
    Filter check alarm(general ventilator)

    165 GUIDE TO DIFFERENT
    MODE OPERATION/OPEN
    SOURCE SOFTWARE
    165
    165

    7

    Different mode operation
    Open Source Software Notice Information

    ENGLISH

    49
    50
    51
    52
    53

    TABLE OF CONTENTS



  • Page 5

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 8

    8

    DESCRIPTION

    READ BEFORE OPERATING THE CONTROLLER

    READ BEFORE OPERATING THE CONTROLLER
    Menu Structure

    NEW STANDARD REMOTE CONTROLLER

    Menu
    Override

    ......................................................................................................................35

    Fine Dust

    ......................................................................................................................36

    Sub function
    Energy Saving

    Operation display
    window

    ..............................................................................39

    Plasma Purification ..............................................................................40

    Back button

    OK

    Up/Down/Left/Right
    Button

    Fan Auto

    ..............................................................................41

    Humidification

    ..............................................................................42

    On/Off Button

    Electric Heater

    ..............................................................................43

    OK Button

    Robot Cleaning

    ..............................................................................44

    Ventilation Kit

    ..............................................................................45

    Comfort Saving

    ..............................................................................46

    Zone Control
    Operation display window

    Operation and Settings status display

    Back button

    When you move to the previous stage from the menu’s setting stage

    Up/down/left/right button

    When you change the menu’s setting value

    OK button

    When you save the menu’s setting value

    On/Off button

    When you turn ON/OFF the air conditioner

    ......................................................................................................................47

    Lock
    All Lock

    ..............................................................................48

    On/Off Lock

    ..............................................................................48

    Mode Lock

    ..............................................................................48

    Set temp range lock ..............................................................................48
    Timer
    Simple Timer

    ..............................................................................50

    Sleep Timer

    ..............................................................................51

    Accessories

    Turn-off reservation ..............................................................................52
    Turn-on reservation ..............................................................................53
    Schedule
    Connecting Cable

    DO Port

    Remote controller
    fixing screws
    (4 EA)

    Quick Guide

    User/Installation
    Manual

    Daily Schedule

    ..............................................................................55

    Schedules & Edit ..............................................................................56
    Exception Day

    ..............................................................................58

    ENGLISH

    DESCRIPTION

    9



  • Page 6

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 10

    10 READ BEFORE OPERATING THE CONTROLLER

    READ BEFORE OPERATING THE CONTROLLER

    ...............................80
    ...............................81

    Home Leave Set Temp ...............................82

    Energy Consumption
    Comfort Cooling

    ...............................83

    Year-on-year Usage

    ..........................61

    Weekly Usage

    ..........................61

    Monthly Usage

    ..........................61

    Defrost Mode

    ...............................84

    Yearly Usage

    ..........................61

    Smart Load Control

    ...............................85

    ODU Refrigerant Noise ...............................83
    Reduction

    Low Noise Mode Time ...............................86

    Energy Saving
    Temp Setback Timer ..........................63
    Time Limit control

    Advanced fan speed “Auto”

    ....................87

    Delay Time(Ventilator) ...............................88

    ..........................64

    Midnight Air Cooling (Ventilator) .................89

    Energy Setting

    Human detection mode ...............................90

    Outdoor Unit Capacity ..........................65
    Target Instantaneous Power ................66

    Discharge direction

    Target Power Consumption ................67
    Target Operation Time ..........................68
    Alarm Popup

    ..........................69

    Usage Data Initialization ..........................70
    Setting
    Function

    ...............................92

    CO2 fan control(Ventilator) ........................92
    User
    Language

    ...............................94

    Setpoint type

    ...............................95

    Temperature Unit

    ...............................96

    Screen Saver Timer

    ...............................97

    LCD Brightness In Idle ...............................97

    Vane Angle Control

    ..........................73

    Elevation Grill

    ..........................74

    External Device

    ...............................98

    Robot Cleaning

    ..........................75

    Date

    .............................101

    Auto Dry

    ..........................75

    Time

    .............................102

    Filter Sign

    ..........................76

    Summer Time

    .............................103

    Password

    .............................104

    Change Temperature ..........................77
    Dead Band

    ..........................78

    Schedule Initialization

    .............................105

    Wi-Fi Paring

    ..........................79

    Theme

    .............................106

    Humidity display

    .............................107

    System Reboot

    .............................108

    ENGLISH

    Zone Naming
    Override Set Time

    Energy
    Instantaneous Power .........................................................................60

    11



  • Page 7

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 12

    12 READ BEFORE OPERATING THE CONTROLLER

    READ BEFORE OPERATING THE CONTROLLER 13

    Service Contact

    ..........................110

    Model Information

    ..........................111

    RMC Version Information

    ..........................112

    Error History

    ..........................113

    Open Source License

    ..........................114

    AC Fan Operation Interlocked .............................145
    With Ventilation
    IDU Auto-Start

    .............................146

    Occupancy Duration Time

    .............................147

    CN_CC

    .............................148

    CN_EXT

    .............................149

    ODU Function Master

    .............................150

    Fan Continuous Operation

    .............................151

    Low Noise Mode Priority

    .............................152

    Installer
    Test Run

    .............................144

    ..........................125

    Central Control Address

    ..........................126

    ESP

    ..........................127

    Temperature Sensor(2TH)

    ..........................128

    Ceiling Height Selection

    ..........................129

    Human detection sensor

    .............................153

    Humidity sensing position

    .............................154

    ODU cycle priority

    .............................155
    .............................157

    Static Pressure

    ..........................130

    RMC Master/Slave

    ..........................131

    Outdoor temp. for heating
    stages

    Override Master/Slave

    ..........................132

    Estimated energy display

    .............................158

    Dry Contact Mode

    ..........................133

    CN_PTC

    .............................158

    Fixed Air Volume

    ..........................134

    Password Initialization

    .............................159

    Zone Type

    ..........................135

    Zone Number

    ..........................135

    Emergency Heater

    ..........................136

    Function Control During Group ..........................137
    Control
    External devices of indoor unit ..........................138
    Expand of Temperature Range ..........................139
    IDU Address Verification

    ..........................140

    Static Pressure Step

    ..........................141

    Guard Timer

    ..........................142

    Fan Speed In Cooling Thermal ..........................143
    off

    Product direction(ventilator) .............................160
    Express ventilation
    priority(Ventilator)

    .............................161

    Humidification of stand-alone .............................162
    ventilation mode(Ventilator)
    Humidification of ventilation with .............................163
    heating operation(Ventilator)
    Ventilation Fan Speed Align- .............................164
    ment(Ventilator)
    Filter check alarm
    (Ventilator)

    Notice
    • Some functions may not work in some indoor unit products.

    .............................164

    ENGLISH

    Primary Heater

    Service



  • Page 8

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 14

    14 DESCRIPTION OF THE OPERATION

    DESCRIPTION OF THE OPERATION 15

    Setting screen
    Select the category to set using [∧,∨(up/down)] button.

    Main screen

    In each detail screen of the menu, as in the box in the left figure,
    when “<,>” icons are displayed at the same time, you can immediately apply the setting value by pressing [<, >(left/right)]
    button.
    ※ For the values that can be set in each category, refer to the
    detail manual for each function.

    In the main screen, press [<, >(left/right)] button to select the category to set, and you can control by pressing [∧,∨ (up/down)] button.

    < Air conditioner main screen>

    <Genernal Ventilation main
    screen>

    In each detail screen of the menu, as in the box in the left figure,
    if only “>” icon is displayed, you can move to the detail setting
    screen by pressing [>(right) or OK] button.
    ※ For the values that can be set in each category, refer to the
    detail manual for each function.

    <Dx Ventilation main screen>

    Menu screen
    In the main screen, press [<, >(left/right)] button to select the menu and press [OK] button to
    move to menu screen.

    Popup screen
    The toast message is the message displayed at the bottom of the screen when an operation is
    turned On/Off or if a function is set / cancelled.
    The popup message is mainly displayed when an error occurred in the product.

    In the menu screen, press [<, >(left/right)] button to select the category to set, and press [OK]
    button to move to the detail screen.

    < Toast message >

    < Popup message >

    ENGLISH

    DESCRIPTION OF THE OPERATION



  • Page 9

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 16

    16 DESCRIPTION OF THE OPERATION

    DESCRIPTION OF THE OPERATION

    Interface screen

    In the main screen, you can enter the monitoring / sub function screen by pressing [Back] button
    and then pressing [<, >(left/right)] button.
    - In the monitoring screen, you can check the indoor temperature and outdoor unit monitoring information.
    - In the sub function screen, you can turn on or off the sub function supported by the product.

    Select the product (air conditioner or ventilation) to set using [<, >(left/right)] button.
    When you control the air conditioner and the ventilation product
    with one remote controller, the screen is displayed as in the side
    figure. You can set the air conditioner by pressing [<(left)] button and pressing [OK] button to move to the air conditioner
    screen.

    When you control the air conditioner and the ventilation product
    with one remote controller, the screen is displayed as in the side
    figure. You can set the ventilation by pressing [>(right)] button
    and pressing [OK] button to move to the ventilation screen.

    Returning to the screen
    In the main screen, after moving to the category by pressing [<, >(left/right)] button, if there is no
    remote controller operation, after 10 seconds, it returns to the main screen basic position. (basic
    position: indoor temperature display part)
    In the screens except the main screen, if there is no remote controller operation for 1 minute, it
    moves to the main screen.

    ENGLISH

    Monitoring / Sub function screen

    17



  • Page 10

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 18

    18 OPERATION SETTING

    OPERATION SETTING 19

    Cooling Operation

    On / Off

    Cooling operation’s minimum setting temperature is 18°C (16°C).
    For some types of the indoor units, the desired temperature can be controlled in the units of 1°C
    or 0.5°C.

    Air conditioner and ventilator will be turned on or off.
    Press the remote controller’s
    (On/Off) button.
    - If the product is in operation, On/Off button will be illuminated.
    If the product is in off, On/Off button backlight will be off.

    - Set the desired temperature lower than the indoor temperature.
    - Indoor temperature is displayed on the default screen of the remote controller.
    - If the setpoint is set higher than the room temperature, then the unit will remain in the cool
    mode but will not begin to cool unit the room temperature exceeds the setpoint.
    - If you unit is operating in cooling mode and you press the [On/Off] button the cooling operation
    will shut off.

    Operation mode
    You can easily control the desired operation mode.
    In the main screen, press [<,>(left/right)] button to select the operation mode or home leave or
    hold category, and press [∧,∨(up/down)] button to set the operation mode.
    ※Some products may not support some operation modes.
    Mode

    Description

    Cool

    Cool the room to the desired temperature.

    Dry

    It removes the moisture with cooling.

    Heat

    Heats the room to the desired room temperature.

    AI / Auto
    Fan
    Power Cool
    Power heating

    The product automatically provides the appropriate fan speed based on
    the temperature of the room.
    Fan only operation, no cooling or heating.
    It provides strong cooling in short time.
    Power heating increases indoor temperature quickly.

    What is 3 minute delay function?
    After the cooling stops, when the product is started right away, the reason that the cold
    wind does not come out is that it is the function to protect the compressor.
    The compressor starts after 3 minutes and the cold wind comes out.

    !

    NOTE

    The compressor starts after 3 minutes and the cold wind comes out.
    In the cooling operation, you can select the desired temperature in the range of 18°C ~ 30°C
    (16°C ~ 30°C).
    The favorable temperature difference between the indoor temperature and the outdoor
    temperature is 5°C.
    For some types of the indoor units, you can select the desired temperature in the range of
    16°C ~ 30°C.

    ENGLISH

    OPERATION SETTING



  • Page 11

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 20

    20 OPERATION SETTING

    OPERATION SETTING 21

    Dry Operation

    The heating operation’s minimum setting temperature is 16°C.
    For some types of the indoor units, the desired temperature can be controlled in the units of 1°C
    or 0.5°C.

    Dry operation’s initial fan speed is “Low”.
    Dry operation does not have a separate desired temperature.

    - Set the desired temperature higher than the indoor temperature.
    - Indoor temperature is displayed on the default screen of the remote controller.
    - When the desired temperature is set lower than the indoor temperature, warm air doesn't
    come out, but for some products, the fan will recirculate room air, or stop altogether.
    - If you unit is operating in heating mode and you press the [On/Off] button the heatling operation
    will shut off.

    - If you unit is operating in dehumidification mode and you press the [On/Off] button the dehumidification operation will shut off.

    !

    NOTE

    If you use it in the rainy season, or when the humidity is high, you can have both the
    effective dehumidification and cooling operation at the same time.

    !

    NOTE

    In the heating operation, you can select the desired temperature in the range of 16°C ~ 30°C.
    Heating operation is operated only in cooling/heating model. The heating is not operated in
    cooling exclusive model.

    ENGLISH

    Heating Operation



  • Page 12

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 22

    22 OPERATION SETTING

    OPERATION SETTING 23

    AI / Auto operation

    Fan only operation’s initial wind strength is “High”.
    Fan only operation does not have a separate desired temperature.

    Auto operation’s initial desired temperature is 25°C.
    The cooling exclusive model’s initial desired temperature is “It’s Fine”.
    Cooling/heating model’s desired temperature can be controlled in the units of 1°C or 0.5°C.
    For cooling exclusive model, the value can be controlled from “hot” stage to “cold” stage.
    - Hot
    - A little hot
    - It’s fine
    - A little cold
    - Cold

    - If you unit is operating in fan only mode and you press the [On/Off] button the the unit will stop.

    - If you unit is operating in ai/auto mode and you press the [On/Off] button the ai/auto operation
    will shut off.

    !

    NOTE

    It provides the Fan only operation without temperature control, with recirculation of indoor
    air.

    !

    NOTE

    If the product is a cooling/heating model, in the auto operation, the desired temperature can
    be selected in the range of 18°C ~ 30°C.
    If it does not operate as you wish, select another operation mode.

    ENGLISH

    Fan Only Operation



  • Page 13

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 24

    24 OPERATION SETTING

    OPERATION SETTING 25

    Power Cool Operation

    The indoor unit automatically manages room temperature with extended heating and cooling setting temperature ranges.
    Dual setpoint auto mode can be set in the USER SETTING. This is recommended in North America region.

    Power cooling quickly lowers the indoor temperature.
    Desired temperature: 18°C
    Fan speed : Power fan speed
    Fan direction: Current fan direction
    - During the power cooling, if fan speed or desired temperature is changed, the power cooling is
    cleared, and it operates in the cooling operation mode.
    - During the power cooling, if you press [On/Off] button, the power cooling operation stops, and
    when you press [On/Off] button again, it operates in the cooling operation mode.

    Power Heat Operation

    !

    NOTE

    • Auto heating function only operates on cooling and heating models.
    • Auto heating function doesn’t operate on cooling only models.
    • When remote controller has a connection with indoor unit that does not support 'dual
    setpoint', thermal operation function of indoor unit is replaced with ON/Off control from the
    wired remote, when the user sets target temperatures in the below ranges.
    - cooling target temp. range : 87~99 °F (30.5~37.5 °C)
    - heating target temp. range : 40~59 °F (4~15.5 °C).

    Power heating increases indoor temperature quickly.
    Desired temperature: 30 °C
    Fan speed: Power fan speed
    Fan direction: Current fan direction
    - If you adjust the fan speed or the desired temperature during power heating, the function is disabled and heating operation mode is activated.
    - If you press [On/Off] button during power heating, the function stops and if you press [On/Off]
    button again, heating operation mode is activated.

    ENGLISH

    Dual setpoint auto operation



  • Page 14

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 26

    26 OPERATION SETTING - VENTILATOR

    TEMPERATURE SETTING 27
    ENGLISH

    OPERATION SETTING - VENTILATOR

    TEMPERATURE SETTING

    Operation mode

    Controlling Desired Temperature

    Ventilation (general and direct cooling type ventilation) operation mode supports the following operation modes.
    ※Some products may not support some operation modes.

    You can easily control to the desired temperature.
    • In the main screen, press [<,>(left/right)] button to select the desired temperature category,
    and press [∧,∨(up/down)] button to set the desired temperature.
    - In the cooling, heating, and AI/auto mode, the desired temperature control is possible.

    Mode
    Auto

    Classification

    Description
    It measures the ventilation system’s indoor temperature and the outdoor temperature for the automatic operation in the optimal ventilation mode state.

    It is the mode of ventilation with both supply/discharge
    Ventilation operation
    through the heat exchanger. It is adequate to use in
    Heat Exchange mode – commonly
    summer/winter where the indoor/outdoor temperature
    supported by ventiladifference is big.
    tion products
    It is the ventilation where the exhausted air is ventilated
    without going through the exchanger. It is adequate to
    Bypass
    use in spring/fall or when the indoor contamination is
    severe.
    Cool
    Heat
    Auto
    Stop

    Cools down the room to desired temperature.
    Air conditioner opera- It provides warm air to the room.
    tion mode – supports
    The product automatically provides the appropriate fan
    direct cooling type
    speed based on the temperature of the room.
    ventilation

    Mode

    Cool

    Heat

    If the desired temperature is lower than the indoor temperature, the heating is not performed.
    Set the desired temperature higher than the indoor temperature.
    You can select in the range of 16°C ~ 30°C.

    It stops the product’s air conditioner operation.

    In the main screen, press [<,>(left/right)] button to select the operation mode category, and press
    [∧,∨(up/down)] button to set the operation mode.

    AI / Auto

    !

    Description
    If the desired temperature is higher than the indoor temperature, the
    cooling is not performed.
    Set the desired temperature lower than the indoor temperature.
    You can select in the range of 18°C ~ 30°C (16°C ~ 30°C).

    For cooling/heating product, you can select in the range of 18°C ~ 30°C.
    For cooling exclusive product, you can select Hot, A little hot, Adequate,
    A little Cold, and Cold.

    NOTE

    The favorable temperature difference between the indoor temperature and the outdoor
    temperature is 5°C.

    ※The direct cooling type ventilation’s air conditioner operation mode is composed separately
    from the ventilation operation mode.



  • Page 15

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 28

    28 TEMPERATURE SETTING

    WIND SETTING 29

    WIND SETTING

    You can check the current indoor temperature.
    • In the remote controller’s the main screen, you can check the indoor temperature.

    Fan speed control
    From the main screen, press [<,>(left/right)] button to select the fan speed category, and press
    [∧,∨(up/down)] button to set the fan speed control the desired fan speed.
    - It circulates in the order of Slow ↔ Low ↔ Medium ↔ High ↔ Power ↔ Auto.

    ※For some product some fan speed may not be available.

    Fan speed control - ventilation

    !

    NOTE

    The temperature distribution in the remote controller installation space is not uniform, so
    there can be a little difference between the temperature you actually feel and the remote
    controller’s room temperature display
    According to Control type setting value
    • Single setpoint
    Fahrenheit: 52~99 °F
    - below 52 °F: display ‘LO’
    - over 99 °F: display ‘HI’
    Celsius: 10.5~39.5 °C
    - below 10.5 °C: display ‘LO’
    - over 39.5 °C: display ‘HI’
    • Dual setpoints
    Fahrenheit: 34~99 °F
    - below 34 °F: display ‘LO’
    - over 99 °F: display ‘HI’
    Celsius: 0.5~39.5 °C
    - below 0.5 °C: display ‘LO’
    - over 39.5 °C: display ‘HI’
    - For indoor temperature below 50 °F (10 °C), the value perceived by the Thermostat(with
    cable) is displayed.

    You can easily control the desired fan speed.
    • In the main screen, press [<,>(left/right)] button to select the fan speed category, and press
    [∧,∨(up/down)] button to set the fan speed.
    - It circulates in the order of low ↔ high ↔ power ↔ auto.

    ※The auto Fan can be used only when the air contamination (CO2) sensor is installed.

    Air flow control
    You can easily control the desired air flow
    • In the main screen, press [<,>(left/right)] button to select the air flow category, and press
    [∧,∨(up/down)] button to set the air flow.
    - It circulates in the order of Off ↔ Up/Down swing ↔ Left/Right swing ↔ Up/Down/Left/Right
    swing ↔ Swirl ↔ Indirect wind ↔ Direct wind↔Human detection direct wind↔Human detection indirect wind.

    • Because of location of Temperature sensing, the real room temperature and the this
    displayed value can be different.

    ※For some product some air flow settings may not be available.

    ENGLISH

    Check Room Temperature



  • Page 16

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 30

    30 HOME LEAVE SETTING

    HOLD SETTING 31

    HOLD SETTING

    Home leave (Unoccupied Mode)

    Hold

    The "Home Leave" function enables proper operation of indoor unit when a space is left for a period of time.
    This feature can only be used when Control type setting is set to the Dual Set Point Control
    mode

    User can use this function when they want to manage indoor unit as home leave control mode
    only.

    !

    NOTE

    User can not change indoor unit status with wired remote controller while set 'home leave
    mode' except for 'home leave mode' release control.
    • Home leave mode will be released if indoor unit operation was changed by commands of
    other controllers(central controller, drycontact and wireless remote controller).
    • When occupied schedule event occurs while operate a home leave mode, home leave
    mode will be released and indoor unit status follow the occupied schedule event.
    • Indoor unit operation change as below when the home leave mode is released.
    - The setpoints and operation mode values are reflected in the control events of the
    scheduled events that are currently applied.
    - If there are no schedule events, the setpoint shall be applied as last setpoints before the
    home leave operation.
    - If there are no setpoints before the 'home leave' operation(dehumidification or fan mode),
    default values will be applied to the setpoints.
    - Default values : dual setpoint auto , heat 60 °F(16 °C), cool 86 °F(30 °C)

    !

    NOTE

    Can not change indoor unit status with wired remote controller while set ‘hold mode' except
    for ‘hold mode' release control.
    • Hold mode will be released if indoor unit operation was changed by commands of other
    controllers(central controller, drycontact and wireless remote controller).
    • A scheduled event is not applied to the indoor unit during a hold mode, even if a scheduled
    event is set.

    ENGLISH

    HOME LEAVE SETTING



  • Page 17

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 32

    32 ADDITIONAL OPERATION –VENTILATION

    EXTERNAL EQUIPMENT CONTROL SETTING 33

    EXTERNAL EQUIPMENT CONTROL SETTING

    Additional operation

    External equipment control

    You can change the additional operation of the ventilation product.
    • In the main screen, press [<,>(left/right)] button to select the additional operation category, and
    press [∧,∨(up/down)] button to set the additional operation.

    It is the function to set the contact point output of the external equipment control mode.
    • In the main screen, press [<,>(left/right)] button to select the external equipment control category, and press [∧,∨(up/down)] button to set the contact point output.

    Additional Operation

    Description

    Mode
    On

    When it is set to “On”, it always performs the contact point output.

    Fast

    It ventilates in short period of time.
    It is the function to operate the ventilation function more efficiently
    through the express setting which is an additional operation of the ventilation product.

    Off

    When you set it to “Off”, it does not perform the contact point output in
    any case.

    Auto

    When it is set to “auto”, the contact point output is decided according to
    the user setting’s external equipment logic setting value.

    Energy saving

    !

    It performs the energy saving function while ventilating efficiently.

    NOTE

    The general ventilation and the direct cooling type ventilation’s additional operation are the
    same.
    The ventilation product’s additional functions (air cleaning / heater / humidification / fan auto)
    setting methods are the same as the air conditioner.

    !

    Description

    NOTE

    Please use the corresponding function when the external equipment is actually connected.
    When the external equipment is not set, please maintain “Off” status.
    For the detail external equipment control condition setting, refer to the user setting - external
    equipment logic setting.

    ENGLISH

    ADDITIONAL OPERATION –VENTILATION



  • Page 18

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 34

    34 PLASMA PURIFICATION SETTING

    OVERRIDE CONTROL SETTING 35

    OVERRIDE CONTROL SETTING

    Plasma Purification

    Override control

    It cleans and makes pleasant indoor air.
    1. Plasma Purification - single operation
    If plasma purification is turned on in operation Off state, plasma purification single operation is
    performed.

    In dual setpoint setting, wired remote controller can manages indoor unit status based on programmed control events which have occupancy option.
    Override control function switches between ‘occupied’ and ‘unoccupied’, and vice-versa.
    User can set timer option which can return to original schedule event in override function menu.

    OK

    In case of plasma purification single operation, it operates in fan mode / automatic wind state,
    and the wind direction operated before the plasma purification single operation is turned off.
    There are 3 ways to end the plasma purification single operation.
    1) Input of On/Off button during plasma purification single operation
    2) Select plasma purification OFF
    3) Change operation mode during plasma purification single operation

    2. Plasma purification - additional operation

    !

    NOTE

    • If mode is changed during plasma purification single operation, it is switched to the air
    cleaning additional operation.
    • Air cleaning operation may not be displayed or performed in some products.

    !

    NOTE

    • If there are no 'occupied' schedule event when operate 'override' control, wired remote
    controller change indoor unit operation as below default setting value.
    - operation mode : Auto
    - target temperature : 86 °F(30 °C)(cool), 60 °F(16 °C)(heat)
    • If there are no ‘unoccupied' schedule event when operate 'override' control, wired remote
    controller change indoor unit operation as 'home leave' mode default value.
    - operation mode : Auto
    - target temperature: 'home leave' target temperature.
    • If wired remote controller received command from other controller, ‘Override’ operation will
    be released.
    • When schedule event occurs while operating an override mode, override mode will be released and indoor unit status follow the schedule event.

    ENGLISH

    PLASMA PURIFICATION SETTING



  • Page 19

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 36

    36 MONITORING SCREEN

    How to enter fine dust status screen
    • In the main screen, press [Back] button to move to monitoring/additional functions screen, and
    press [<, > (left/right)] button to move to fine dust status screen. (Method 1)

    Fine dusts status
    It is the function to monitor dust value measured by the dust sensor mounted inside the air conditioner.
    • In the fine dust status screen, you can check fine dust, ultra fine dust, and super ultra fine dust
    concentration values.
    • The overall index displays the worst dust status value among the three dust status values.

    • In the menu screen, press [<, > (left/right)] button to select the fine dust screen category, and
    press [OK] button to move to the fine dust status screen. (Method 2)

    !

    NOTE

    • The fine dust status may not be displayed in some products.
    • Fine dust status can be checked only when the product is in operation.

    ENGLISH

    MONITORING SCREEN

    MONITORING SCREEN 37



  • Page 20

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 38

    38 SUB FUNCTION SETTING

    SUB FUNCTION SETTING 39

    Energy Saving Setting

    Sub function entrance and setting method

    The energy saving cooling function is the function to control the desired temperature during the
    cooling operation to improve the comfort of the user and to improve the power saving performance.

    In the menu screen, press [<,>(left/right)] button to select the sub function category, and press
    [OK] button to move to the sub function setting list screen.
    In the sub function setting list screen, if you press [<, >(left/right)] button, you can turn on/off the
    corresponding sub function. (method 1)
    In the main screen, press [Back] button to move to the monitoring/sub function screen, and press
    [<,>(left/right)] button to move to the sub function screen. In the sub function screen, select the
    sub function category to set, and if you press [OK] button, you can turn on/off the corresponding
    function. (method 2)

    !

    NOTE

    The energy saving function is an additional function, and it may not be displayed/operated in
    some products.
    The energy saving function is possible only when the product is in the cooling operation.

    ENGLISH

    SUB FUNCTION SETTING



  • Page 21

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 40

    40 SUB FUNCTION SETTING

    SUB FUNCTION SETTING 41

    Fan Auto Setting

    It makes the indoor air clean and pleasant.

    Select fan operation after performing thermal control of indoor units.
    If set to 'ON', fan operation keeps on after thermal operation of indoor units.

    !

    NOTE

    The air cleaning function is an additional function, and it may not be displayed/operated in
    some products.
    The air cleaning function is possible only when the product is in operation.
    If you want air cleaning single operation, set air cleaning in the wind only operation.

    !

    NOTE

    The fan auto function is an additional function, and it may not be displayed/operated in some
    products.

    ENGLISH

    Plasma Purification Setting



  • Page 22

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 42

    42 SUB FUNCTION SETTING

    SUB FUNCTION SETTING 43

    Electric Heater Setting

    It is the function to activate the humidifier installed in the product when the indoor air is dry.

    It is the function to reinforce the heating capability by turning on the electric heater during the
    heating operation.

    !

    NOTE

    The humidification function is an additional function, and it may not be displayed/operated in
    some products.

    !

    NOTE

    It can be set only in the heating operation.
    The heater function is an additional function, and it may not be displayed/operated in some
    products.

    ENGLISH

    Humidification setting



  • Page 23

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 44

    44 SUB FUNCTION SETTING

    SUB FUNCTION SETTING 45

    Ventilation kit Setting

    Robot cleaning function is the function to automatically perform the filter cleaning with the
    cleaner in the product when the air conditioner is used for certain period of time.

    Function enables operation of an optional ventilation kit with indoor units

    !

    NOTE

    It can be set 30 seconds after the operation stopped.
    The robot cleaning function is an additional function, and it may not be displayed/operated in
    some products.

    !

    NOTE

    The ventilation kit function is an additional function, and it may not be displayed/operated in
    some products.

    ENGLISH

    Robot Cleaning Setting



  • Page 24

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 46

    46 SUB FUNCTION SETTING

    ZONE CONTROL SETTING 47

    ZONE CONTROL SETTING

    The comfort cooling is the function to automatically control the cooling strength to maintain the
    pleasant feeling without turning off the product after the indoor temperature reached the desired
    temperature.

    Zone Control
    A function to control zone with duct type indoor units.
    Wired Remote controller can control maximum 8 zones.

    OK

    !

    NOTE

    The comfort cooling function is an additional function, and it may not be displayed/operated in
    some products.
    The comfort cooling function is only possible when the product is in the cooling operation.

    !

    NOTE

    According to installation setting value
    • If no function is supported this entry can not function.
    • Old type
    - Zone control is currently only available to monitor.
    • New type(4zone or 8Zone)
    - Any number of zones is installed is displayed on the screen can be controlled.

    ENGLISH

    Comfort Cooling Setting



  • Page 25

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 48

    48 LOCK SETTING

    TIMER SETTING 49
    ENGLISH

    LOCK SETTING

    TIMER SETTING

    How to enter lock setting

    Timer entrance and setting method

    • In the menu screen, press [<,>(left/right)] button to select “lock setting” category, and press
    [OK] button to move to the lock setting list screen.
    • In the lock setting list, if you press [∧ ,∨(up/down)] button, you can turn on/off the corresponding lock function.

    • In the menu screen, press [<,>(left/right)] button to select the timer category, and press [OK]
    button to move to the timer setting list screen.
    • In the timer setting list screen, press [∧,∨(up/down)] button to select the timer to set, and
    press [OK] button to move to the detail screen.
    • After setting the value, when you press [OK] button, the timer is activated.
    • After setting the value, if you press [Back] button, the changed value will not be applied.

    OK

    OK
    Lock setting – all, on/off, mode, temperature range lock
    • It is the function to lock the button operation of the remote controller so that children or other
    persons cannot use it without permission.
    • It is the function to limit the desired temperature range that can be set in the wired remote controller.
    Lock
    All lock
    On/Off lock

    It locks the On/Off button operation of the remote controller.

    Mode lock

    It locks the operation mode button operation of the remote controller.

    Temperature range
    lock

    !

    Description
    It locks all button operation of the remote controller.

    It is the function that can limit the range of the desired temperature that
    can be set in the wired remote controller.
    - Single: Lower limit : 16~30 °C (60~86 °F)
    Upper limit : 16/18~30 °C (60/64~86 °F)
    - Dual : Cooling : 50~99 °F (10~37.5 °C)
    Heating : 40~90 °F (4~32 °C)

    NOTE

    In the central controller, when the central control temperature range lock is set, the wired
    remote controller’s temperature lock setting is cleared.
    The temperature change by external equipment is reflected regardless of the remote
    controller temperature range lock.



  • Page 26

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 50

    50 TIMER SETTING

    TIMER SETTING 51

    Sleep timer

    You can easily set the timer in the range of 1~7 hours in the units of 1 hour.

    Sleep timer is the function to operate the air conditioner in sleep mode before going to sleep for
    certain hours and stop the operation.

    OK

    !

    NOTE

    If the product operation is On, the easy timer turns off the operation after the corresponding
    time.
    If the product operation is Off, the easy timer turns on the operation after the corresponding
    time.
    If the easy timer operation is turned On/Off before the timer operation, the set timer will be
    cleared.

    OK

    !

    NOTE

    You can set the sleep timer while the product is in operation.
    If the sleep timer operation is turned On before the timer operation, the set timer will be
    cleared.

    ENGLISH

    Simple timer



  • Page 27

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 52

    52 TIMER SETTING

    TIMER SETTING 53

    Turn-on Reservation

    The product is automatically turned Off at the set timer time.

    The product is automatically turned On at the set timer time.

    OK

    !

    NOTE

    Even if the Turn-off Reservation operation is turned On/Off after the setting and before the
    timer operation, the set timer is not cleared.

    OK

    !

    NOTE

    Even if the Turn-on Reseravation operation is turned On/Off after the setting and before the
    timer operation, the set timer is not cleared.

    ENGLISH

    Turn-off Reservation



  • Page 28

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 54

    54 SCHEDULE SETTING

    SCHEDULE SETTING 55

    Daily Schedule

    How to enter schedule

    It is the function that can check the status of the timer (schedule) saved in the remote controller.
    • In the schedule list, select the daily schedule status category, and press [OK] button to move to
    the detail daily schedule status screen.

    • In the menu screen, press [<,>(left/right)] button so select the schedule category, and press
    [OK] button to move to the schedule setting list screen.
    • In the schedule setting list screen, press [∧,∨(up/down)] button to select the menu to set, and
    press [OK] button to move to the detail screen.

    • You can use the remote controller’s [<,>(left/right)] button to check the timer information of
    other dates.

    • You can use the remote controller’s [∧,∨(up/down)] button to check the corresponding date’s
    other timer information.

    OK

    • Select the timer information, and press [OK] button to move to the corresponding timer’s edit
    screen.

    !

    NOTE

    In the daily schedule status screen, even if the timer (schedule) is set, if the corresponding
    date is designated as an exception date, the schedule will not be performed.
    Less than 5 schedules per day is recommended.

    ENGLISH

    SCHEDULE SETTING



  • Page 29

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 56

    56 SCHEDULE SETTING

    SCHEDULE SETTING 57

    Schedules & Edit – Add schedule

    It is the function that can check the status of the timer (schedule) saved in the remote controller.

    Description of each stage in Add schedule

    ENGLISH

    Schedules & Edit
    • In the schedule list, select the daily schedule status category, and press [OK] button to move to
    the daily schedule status detail screen.
    • You can use the remote controller’s [<,>(left/right)] button to check other date’s timer information.
    You can check the set
    timer’s operation information (operation
    On/Off, operation
    mode, desired temperature), timer time, period,
    and day of week.

    Stage 1. Period setting

    Stage 2. Day of week setting

    • You can edit the saved schedule’s timer information.
    - Select the schedule to edit using [∧,∨(up/down)] button, and press [OK] button to move to
    the edit screen.

    Stage 3. Time setting

    Stage 4. Operation setting

    • Select the timer information, and press [OK] button to move to the corresponding timer’s edit
    screen.

    Add schedule is completed

    < If schedule is changed >

    < If schedule is deleted >

    In ‘Stage 1’, it sets the period to perform the timer.
    In ‘Stage 2’, it sets the day of week to perform the timer.
    - You can select ‘Everyday / Weekend / Weekdays / Individual selection’.
    In ‘Stage 3’, it sets the start time for the timer.
    In ‘Stage 4’, it sets the timer operation information.
    - If ‘Stop’ is selected, you cannot set the mode / temperature / fan speed.
    When stages 1~4 are completed, along with the message of ‘schedule is added’, it moves to
    View and edit schedule screen.



  • Page 30

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 58

    58 SCHEDULE SETTING

    It is the function to automatically stop the operation on the set timer day.
    • In the schedule list, select the exception day category, and press [OK] button to move to the
    Exception day designation detail screen.
    • In the exception day, you can check, and add/change/delete the exception day information
    saved in the remote controller.
    - To add an exception day, in the Exception day registration detail screen, designate
    year/month/day, and press [OK] button to save the Exception day.
    - Select the Exception day to edit using [∧,∨(up/down)] button, and press [OK] button to move
    to the edit screen.

    ENERGY (air conditioner / DX ventilator)
    How to enter energy
    • In the menu screen, press [<,>(left/right)] button to select the energy category, and press [OK]
    button to move to the energy list.

    OK
    - In the exception day edit screen, you can check, delete/change the corresponding exception
    day’s setting contents.
    - When you change the exception day information, you need to save it after the change.

    ENGLISH

    Exception day

    ENERGY 59



  • Page 31

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 60

    60 ENERGY

    ENERGY 61

    Energy consumption

    It is the function that can check the product’s instantaneous power.
    ※There may be some error with the actual instantaneous power, so use it only for reference.
    • In the energy list, select the “Instantaneous power” category, and press [OK] button to move
    to the detail screen.

    You can check the energy consumption (operation time, power consumption).
    ※There may be some error with the actual consumption, so use it only for reference.
    • In the energy list, select the “energy consumption” category, and press [OK] button to move to
    the detail screen.

    OK

    OK

    • In the detail screen, press [<,>(left/right)] button to move to the power consumption and operation time screen.

    • The target and the value of all can be set in the energy setting.
    • The usage ratio compared to the target is the value expressed in current/target * 100.
    ※For how to set the energy, refer to the energy setting.

    !

    NOTE

    Instantaneous power: It is the power currently used in the product.

    <, >

    ENGLISH

    Instantaneous power check



  • Page 32

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 62

    62 ENERGY

    ENERGY 63

    List

    Description
    Power consumption

    Operation time

    You can see the power consumption compared to the same month
    of the previous year.

    You can see the operation time
    compared to the same month of
    the previous year.

    Weekly usage

    It displays the daily power consumption of the current month.

    It displays the daily operation time
    of the current month.

    Monthly usage

    It displays the weekly power consumption of the current month.

    It displays the weekly operation
    time of the current month.

    Year On Year Usage

    Yearly usage

    Energy saving - Temperature Setback Timer
    It is the function to return to the desired temperature after the set time after the product operation for energy saving.
    • In the energy list, select “Energy saving” category, and press [OK] button to move to the energy saving screen.
    • In the energy saving list, select “Temperature Setback Timer” category, and press [OK] button
    to move to the Temperature Setback Timer setting screen.

    It displays the monthly power con- It displays the monthly operation
    sumption of the current year.
    time of the current year.

    OK

    OK

    • When it is set to On, you can set the time (10 minutes ~ 120 minutes, 10 minutes unit) and the
    temperature (18°C ~ 30°C), and after the setting, when you press [OK] button, the set value is
    saved.
    • When the desired temperature setback timer setting is set to “On”, after the set time, the desired temperature is recovered to the set temperature.

    !

    NOTE

    When it is set at the same time with the remote controller desired temperature range lock or
    the central control temperature range lock, it may not return to the desired temperature.

    ENGLISH

    • Operation time unit is time (hr.), and power consumption unit is kWh.
    • The power consumption display can be checked when it is connected to the indoor unit that
    supports the power consumption information display function.



  • Page 33

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 64

    64 ENERGY

    ENERGY 65

    Energy setting - outdoor unit capacity setting

    It is the function to stop the product operation after the set time after starting the product operation for the energy saving.
    • In the energy saving list, select “time limit control” category, and press [OK] button to move to
    the time limit control setting screen.

    It is the function that can set the outdoor unit capacity.
    • In the energy list, select “energy setting” category, and press [OK] button to move to the energy setting screen.
    • In the energy setting list, select “outdoor unit capacity setting” category, and press [OK] button
    to move to the outdoor unit capacity setting screen.

    OK
    OK

    OK
    OK

    • In the detail screen, you can select “On/Off” to turn on and off the time limit control function.
    When it is set to On, you can set the time (30 minutes ~ 540 minutes, 30 minutes unit), and
    after the setting, if you press [OK] button, the set value is saved.
    If you do not press [OK] button but press [Back] button, it moves to the list screen without saving the set value.
    • If the time limit control is set to “On”, the operation stops after the set time.

    !

    NOTE

    If it is set at the same time with the remote controller operation lock, the time limit control
    will not be performed.

    • In the detail screen, you can select “On/Off” to set the outdoor unit capacity. If it is set to On,
    you can set the outdoor unit capacity (minimum 1kW), and after the setting, if you press [OK]
    button, the set value is saved. If you do not press [OK] button but press “Back’ button, it
    moves to the list screen without saving the set value.
    • If the capacity setting is set to “On”, in the Instantaneous power screen, it is displayed as “all”
    capacity.
    • For the outdoor unit capacity, refer to the label of the outdoor unit product.
    - For Single product and Multi product, the first 3 digits of the model name is the outdoor unit
    capacity.
    ex) For ABC1019…, it is 10.1kW
    - For Multi-V product, the first 2 digits of the model name < 0.75 is the outdoor unit capacity.
    ex) For ABCD101.…, it is 10 * 0.75 = 7.5kW
    • For TMS users, refer to the all capacity displayed on TMS.

    !

    NOTE

    According to the user input, there may be difference to the actual product capacity.

    ENGLISH

    Energy saving - Time Limit Control



  • Page 34

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 66

    66 ENERGY

    ENERGY 67

    Energy setting - target power consumption

    It is the function that can set the Instantaneous power’s target value.
    You can set the target value to find the power consumption status.
    • In the energy setting list, select “target Instantaneous power” category, and press [OK] button
    to move to the target Instantaneous power setting screen.

    It is the function to set the target power consumption per hour.
    • In the energy setting list, select “target power consumption” setting category, and press [OK]
    button to move to the target power consumption setting screen.

    OK
    OK

    OK
    OK

    • In the detail screen, you can select “On/Off” to set the target Instantaneous power.
    If it is set to On, you can set the target Instantaneous power (minimum 1kW), and after the
    setting, if you press [OK] button, the set value is saved.
    - If the outdoor unit capacity is set, the maximum value is the outdoor unit capacity
    - If the outdoor unit capacity is not set, the maximum value is 9999kW
    If you do not press [OK] button but press “Back’ button, it moves to the list screen without
    saving the set value.
    • When the target Instantaneous power setting is set to “On”, in the Instantaneous power
    screen, it is displayed as “all” capacity.

    • In the detail screen, you can select “On/Off” to set the target power consumption.
    When it is set to On, you can set the target power consumption (minimum 1kWh, maximum
    100kWh), and after the setting, if you press [OK] button, the set value is saved.
    If you do not press [OK] button but press “Back’ button, it moves to the list screen without
    saving the set value.
    • If the target power consumption setting is set to “On”, it is displayed as the energy
    consumption’s power consumption target value.
    - Daily target consumption: Weekly usage’s daily target
    - Weekly target consumption: Monthly usage’s weekly target (daily target * 7)
    - Monthly target consumption: Yearly usage’s monthly target (daily target * 31)

    ENGLISH

    Energy setting - target instantaneous power setting



  • Page 35

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 68

    68 ENERGY

    ENERGY 69

    Energy setting - Alarm Popup Setting

    It is the function that can set the Instantaneous power’s target value.
    You can find the power consumption status by setting the target value.
    • In the energy setting list, select “target operation time” category, and press [OK] button to
    move to the target operation time setting screen.

    It is the function to set whether to use the target power consumption and the target operation
    time notice popup window.
    • In the energy setting list, select “target operation time” category, and press [OK] button to
    move to the target operation time setting screen.
    • In the notice popup list, select “target power consumption notice or target operation time notice” category, and press [OK] button to move to the detail setting screen.

    OK

    OK
    OK
    OK
    OK

    • In the detail screen, you can select “On/Off” to set the target operation time.
    When it is set to On, you can set the target operation time (minimum 1hr. and maximum 24hr.),
    and after the setting, if you press [OK] button, the set value is saved.
    If you do not press [OK] button but press “Back’ button, it moves to the list screen without
    saving the set value.
    • If the target operation time setting is set to “On”, it is displayed as the energy consumption’s
    operation time target value.
    - Daily target : Weekly usage’s daily target
    - Weekly target : Monthly usage’s weekly target (daily target * 7)

    • You can set the notice popup as “daily”, “weekly”, “monthly”.
    After the setting, if you press [OK] button, the setting is saved and moves to the previous
    screen.
    • When the target power consumption notice is set to “On, daily”
    If the daily target power consumption’s 80%, 90%, 95%, and 100% power is used a day, the
    popup screen appears.
    • When the target operation time notice is set to “On, daily”
    When the product is operated at the daily target operation time’s 80%, 90%, 95%, and 100%,
    the popup screen appears.

    - Monthly target : Yearly usage’s monthly target (daily target * 31)

    !

    NOTE

    The popup message appears once every hour.

    ENGLISH

    Energy setting - target operation time



  • Page 36

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 70

    70 ENERGY

    FUNCTION SETTING

    FUNCTION SETTING

    It is the function to initialize all of the power consumption and operation time information.
    • In the energy setting list, select “consumption data initialization” category, and press [OK] button to move to the consumption data initialization setting screen.

    How to enter function setting

    OK

    ENGLISH

    Energy setting – Usage data initialization

    To enter the menu displayed at the bottom, you need to enter the function setting menu as follows.
    • In the menu screen, press [<,>(left/right)] button to select the setting category, and press [OK]
    button to move to the setting list.
    • In the setting list, select the function setting category, and press [OK] button to move to the
    function setting list.

    OK

    OK

    OK
    • In the initialization popup screen, if you press “check” button, all previously saved power consumption and operation time are deleted.

    71



  • Page 37

    1,MFL69312302,영영 2018. 11. 19. 영영 11:18 Page 72

    72 FUNCTION SETTING

    FUNCTION SETTING 73

    Menu
    Vane angle control setting
    Elevation grill setting

    Vane angle control setting
    Description
    You can control the wind blowing angle.
    It is the function to operate the Elevation grill for the indoor unit filter cleaning.

    Robot cleaning setting

    Robot cleaning function is the function to automatically perform the filter
    cleaning with the cleaner of the product when the air conditioner is used for
    certain time period. It sets the manual or automatic operation of the robot
    cleaning. You can set it 30 seconds after the stopping of the operation.

    Auto dry setting

    Auto dry function is the function to remove mold and moisture by drying the inside of the indoor unit after the cooling operation and when
    the product is turned off.

    You can control the wind blowing angle.
    - In the function setting list screen, press [∧,∨(up/down)] button to select the vane angle control
    category, and press [OK] button to move to the up/down vane angle detail screen.

    Filter sign check and ini- When it becomes the time for the indoor unit filter cleaning, the filter
    tialization
    cleaning display appears, and it is the function to remove the display.
    Change Temperature
    setting

    Change Temperature is the function to set the temperature for the automatic conversion between cooling and heating according to the
    temperature in AI operation mode.

    Dead Band

    When heating and cooling desired temperatures have been changed,
    the set value will maintain a difference between the heating and cooling desired temperature.

    Wi-Fi pairing

    OK

    It is the function to perform the pairing function of the Wi-Fi module
    connected to the indoor.

    Zone Name setting
    Zone name settings allow you to select zone name.
    Override set time setting When timed override is used, the set time will be a default value.
    Home leave set temper- When customer operate as home leave mode, this setting temperaature setting
    ture value will be applied.
    Comfort cooling setting

    It is the function to set the outdoor unit Comfort saving operation
    stage value.

    ODU Refrigerant Noise It is the function to set the outdoor unit’s refrigerant noise reduction
    Reduction setting
    function.
    Defrost Mode setting
    Smart load control
    setting
    Low noise mode time
    setting

    It is the function to set the outdoor unit’s defrost mode operation.
    It is the function to set the outdoor unit’s smart load control stage value.
    (Smart load control is the function to calculate the necessary performance
    with the indoor and outdoor air temperature and humidity and operate.)
    It is the function to set the start and end time of the outdoor unit’s
    low noise mode operation.

    • In the detail screen, press [∧,∨(up/down)] button to select “individual control, overall control,
    standard”.
    • Use [<,>(left/right)] button to select the vane.
    - The selected vane is moving. Check the moving vane.
    • Press [∧,∨ (up/down)] button to select the desired wind angle, and press [OK] button to save
    the setting.
    - The wind angle’s setting range can be changed to 5 stages or 6 stages according to the product.
    ※If you do not press [OK] button, the selected wind angle will not be reflected.

    Advanced fan speed “Auto” It is the function to set the indoor unit’s fan auto by temperature.

    Control

    Delay time setting (ex- It is the function to set the ventilation operation to start after the delay
    clusive for ventilation) time.

    Each
    All

    Midnight air cooling
    (ventilation interface)

    It is the function to discharge indoor air and supply cool outdoor air
    into the indoor during summer nights to save energy.

    Human detection mode It is the function to set the operation of human detection mode.
    Discharge direction
    CO2 fan control

    This is a function to set the usage of the upper and lower vanes when
    operating the product.
    A function that controls the fan when the product is turned ON/OFF,
    based on the CO2 concentration in the ventilation product.

    Standard

    !

    Description
    It sets the vane angle individually.
    It sets the vane angle of all the vanes of the product at once.
    It sets the vane angle to the factory initialization state.

    NOTE

    For some product types, there are products with only 1 or 2 vanes.

    ENGLISH

    Function Setting



  • Page 38

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 74

    74 FUNCTION SETTING

    FUNCTION SETTING 75

    Robot cleaning setting

    It is the function to operate the Elevation grill for the indoor unit filter cleaning.
    - While the product operation is stopped, if you use [<,>(left/right)] button to select the setting
    value, the grill operation status changes.

    Robot cleaning function is the function to perform the automatic filter cleaning with the cleaner
    of the product when the conditioner is used for certain period of time. It sets the manual or automatic operation of the robot cleaning.
    - It can be set 30 seconds after the operation stop.
    • You can use [<,>(left/right)] button to set the following setting values as follows.

    Value
    Up

    !

    Description
    Stops the movement of the Elevation grill

    Down

    Lowers the Elevation grill toward the floor

    NOTE

    The Elevation grill setting function may not work in some products.

    Description

    Auto

    It automatically performs the robot cleaning when the accumulated indoor unit operation time passes 30 hours

    Manual

    Raises the Elevation grill toward the product

    Stop

    Value

    !

    It manually performs the robot cleaning.

    NOTE

    The robot cleaning setting function may not work in some products.

    Auto dry setting
    Auto dry function is the function to remove mold and moisture by drying inside the indoor unit
    after the cooling operation and when the product is turned off.
    • You can use [<,>(left/right)] button to set the following setting values as follows.

    Value
    Use
    Not Use

    !

    Description
    Use auto dry function
    Not use auto dry function

    NOTE

    Auto dry setting function may not work in some products.

    ENGLISH

    Elevation grill setting



  • Page 39

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 76

    76 FUNCTION SETTING

    FUNCTION SETTING 77

    Change temperature setting
    Change Temperature is the function to set the automatic Change Temperature between cooling
    and heating operation according to the temperature in AI operation mode.
    • In the function setting list, select the Change Temperature category, and press [OK] button to
    move to the detail screen.

    OK

    OK

    Value
    1~7°C(Default : 2°C)
    It is the function that can be used only in cooling/heating product.
    Filter sign
    Good

    Description
    Usage time is 70% or less

    Normal

    Usage time is 71~80%

    Caution

    Usage time is 81~99%

    Bad

    Usage time is 100%

    - When it becomes time to the filter clean, “Filter cleaning or replacement is required.” message
    is displayed. Enter the Filter sign check and initialization detail screen.
    - If the product has the function to display the time remaining until the filter cleaning, even if the
    filter cleaning message is not displayed, you can enter the Filter sign check and initialization.
    - If there is a remaining time display function, when you enter the Filter sign detail screen, you
    can see the consumption and the remaining time.

    !

    NOTE

    • Some products have a Filter Time Remaining function that can be accessed with Filter Sign
    check.
    • Dirty filters will increase the cost to cool or heat the conditioned space.
    • The filter check message is cleared after certain time without a separate clearing.

    Example of using Change Temperature
    Condition
    1) Mode: AI mode
    2) temperature: 22°C
    3) Change Temperature: 3°C → Change Temperature 3°C difference
    ※In case of the above conditions, it operates as in the graph.
    Temp(ഒ)

    ‫ڸ‬

    ‫ڸ‬

    25ഒ

    ‫ ڸ‬: Cooling operation start
    ‫ ڹ‬: Heating operation start

    22ഒ
    19ഒ
    ‫ڹ‬

    !

    NOTE

    The Change Temperature setting function may not work in some products.

    ENGLISH

    Filter sign check and initialization
    When it becomes the time for the indoor unit filter cleaning, the filter cleaning message appears,
    and it is the function to remove the message.
    • In the function setting list, select the Filter sign check and initialization category, and press [OK]
    button to display the detail screen.



  • Page 40

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 78

    78 FUNCTION SETTING

    FUNCTION SETTING 79

    Wi-Fi pairing setting

    Dead Band function is used with a dual setpoint mode.
    When heating and cooling desired temperatures have been changed, the set value will maintain a
    difference between the heating and cooling desired temperature.
    • In the function setting list, select the dead band category, and press [OK] button to move to the
    detail screen.

    It is the function to perform the pairing function of the Wi-Fi module connected to the indoor unit.
    • In the function setting list, select the Wi-Fi pairing category, and press [OK] button to move to
    the detail screen.
    - After selecting “Apply”, if you press [OK] button, the Wi-Fi pairing popup window is created,
    select “check” and press [OK] button to request the Wi-Fi pairing.

    OK
    OK

    !

    NOTE

    Dead Band function only can use in dual setpoint mode.
    • When changing the desired cooling temperature, in case of that the difference with the
    heating temperature becomes lesser than its minimal value of difference, it lowers the
    desired heating temperature automatically.
    • When changing the desired heating temperature, in case of that the difference with the
    heating temperature becomes lesser than its minimal value of difference, it raises the
    desired cooling temperature automatically.

    !

    NOTE

    The Wi-Fi setting function may not work in some products.

    ENGLISH

    Dead Band



  • Page 41

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 80

    80 FUNCTION SETTING

    FUNCTION SETTING 81

    Override Set Time Setting

    Zone name settings allow you to select zone name.

    Override Set Time function can only be used in Dual Setpoint Control mode.
    When timed override is used, the set time will be a default value.

    OK

    OK

    OK
    !

    NOTE

    Override Set Time function can only be used in a dual setpoint control mode.

    !

    NOTE

    Zone name setting function may not work in some indoor unit products.

    ENGLISH

    Zone Name setting



  • Page 42

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 82

    82 FUNCTION SETTING

    FUNCTION SETTING 83

    Comfort cooling setting

    Home Leave Set Temperature function is used in Dual Setpoint Control mode.
    When customer operate as home leave mode, this setting temperature value will be applied.

    It is the function to set the outdoor unit Comfort saving operation value.
    • You can set the following values using [<,>(left/right)] button.

    Value
    Step 1

    OK

    Step 2
    Step 3

    !

    NOTE

    The Comfort cooling function does not work in the group control.
    Comfort cooling setting function is only available in some products.

    ODU Refrigerant Noise Reduction setting
    It is the function to set the outdoor unit’s refrigerant noise reduction function.
    • You can use [<,>(left/right)] button to set the following setting values as follows.

    !

    NOTE

    Home Leave Set Temperature function can only be used in a dual setpoint control mode.

    Value

    !

    Description

    Step 0

    Not use

    Step 1

    Outdoor unit noise mode 1

    Step 2

    Outdoor unit noise mode 2

    NOTE

    The ODU Refrigerant Noise Reduction function can be set only when the installer setting’s
    outdoor unit function M/S setting is set to “Master”.
    ODU Refrigerant Noise Reduction function is only available in some products.

    ENGLISH

    Home Leave Set Temperature Setting



  • Page 43

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 84

    84 FUNCTION SETTING

    FUNCTION SETTING 85

    Smart load control(SLC) setting

    Change the outdoor unit’s defrost mode operation.
    • Select value using [<,>(left/right)] button.

    Change the outdoor unit’s Smart Load Control stage value.
    (Smart load control is the function to calculate the indoor air temperature, outdoor air temperature, and humidity to operate effectivly.)
    • In the function setting list, select the Smart load control category, and press [OK] button to
    move to the detail screen.

    Value

    !

    Step 0

    Not use

    Step 1

    Forced snow removal

    Step 2

    Quick defrost

    Step 3

    Forced snow removal + quick defrost

    OK

    NOTE

    The Defrost mode setting function can be set only when the installer setting’s outdoor unit
    function M/S setting is set to “Master”.
    Defrost mode setting function is only available in some products.

    Off

    Step 0
    Step 1

    Value

    On

    Step 2
    Step 3
    Step 4

    - When SLC is Operating, on the expanded screen’s monitoring information, ‘In Smart load control’ is displayed.

    !

    NOTE

    Smart load control function can be set only when the installer setting’s outdoor unit function
    M/S setting is set to “Master”.
    Smart load control function is only available in some products.
    Step4 settings may not be available on some indoor unit products.

    ENGLISH

    Defrost mode setting



  • Page 44

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 86

    86 FUNCTION SETTING

    FUNCTION SETTING 87

    Advanced fan speed “Auto” setting

    It is the function to set the start and end time of the outdoor unit’s low noise mode operation.
    • In the function setting list, select the Low Noise Mode Time category, and press [OK] button to
    move to the detail screen.
    - After setting the start time and the end time, press [OK] button to move to the upper level
    list.
    - If the start time and the current time are the same, it enters the outdoor unit low noise operation mode, and in the monitoring screen, ‘in outdoor unit low noise operation mode’ message
    is displayed.
    - If the end time and the current time are the same, the outdoor unit low noise operation mode
    is cleared.

    It is the function to set the indoor unit’s temperature based auto fan usage.
    It is the function to automatically change the fan speed according to the difference between the
    indoor temperature and the desired temperature.
    • You can set the following setting values using [<,>(left/right)] button.

    Value
    Set
    Clear

    Description
    Do not change the fan speed automatically
    Change the fan speed automatically

    OK
    !

    NOTE

    Advanced fan speed “Auto” setting function is only available in some products.

    !

    NOTE

    Low noise mode time setting function can be set only when the installer setting’s outdoor
    unit function M/S setting is set to “Master”.
    Low noise mode time setting function is only available in some products.

    ! CAUTION
    If the function is not used, please set it to Off.
    When you enter the low noise operation, the cooling capacity may be degraded.

    ENGLISH

    Low noise mode time setting



  • Page 45

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 88

    88 FUNCTION SETTING

    FUNCTION SETTING 89

    Midnight air cooling (ventilation interface)

    It is the function to set the ventilation operation to start after the delay time.
    • In the function setting list, select the delay time category, and press [OK] button to move to the
    detail screen.
    - After setting the minute, press [OK] button to move to the upper level list.

    It is the function to discharge indoor air and supply cool outdoor air into the indoor during summer nights to save energy.
    • In the function setting list, if you select midnight outdoor air cooling category and press [OK]
    button, it moves to the detail screen.
    - When you set the start and end time and press [OK] button, it saves and moves to the upper
    level list.

    OK

    Value
    0 ~ 60 Minutes

    OK

    !

    NOTE

    Whether to run the midnight air cooling is decided only when both air conditioner and
    ventilation are stopped.
    • Even if it is the set midnight air cooling time, it enters the midnight air cooling only when
    the outdoor temperature conditions is met.
    • During the midnight air cooling operation, “in midnight outdoor air cooling” message is
    displayed on the monitoring screen.
    • Midnight air cooling function may not work in some products.

    ! CAUTION
    . If you do not use the function, please set it as off.

    ENGLISH

    Delay time (exclusive for ventilation)



  • Page 46

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 90

    90 FUNCTION SETTING

    FUNCTION SETTING 91
    ENGLISH

    Human detection mode setting
    It is the function that enables energy saving through the human detection power saving operation
    and wind direction setting.
    In the function setting list, select human detection operation mode category and press [OK] button to move to the lower level setting list.

    After selecting human detection wind direction category, you can set the following setting values
    using [<,> (left/right)] button.
    Value
    OFF
    Direct

    OK

    Indirect

    !

    Description
    Do not use human detection wind direction control
    Human detection direct wind operation
    Human detection indirect wind operation

    NOTE

    Human detection operation setting function may not work in some products.

    After selecting human detection power saving mode category, if you press [OK] button, it moves
    to the detail screen.

    You can select OFF ← → On/Off Power saving ← → Temperature power saving for mode value.
    You can set the time value when you select On/Off power saving or Temperature power saving.



  • Page 47

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 92

    92 FUNCTION SETTING

    USER SETTING 93

    USER SETTING

    This is a function to set the usage of the upper and lower vanes when operating the product.
    You can set the following setting values using [<,>(left/right)] button.

    How to enter user setting

    ENGLISH

    Discharge direction

    To enter the menu displayed at the bottom, you need to enter the user setting menu as follows.
    • Select the setting category, and press [OK] button to move to the setting list.
    • Select the user setting category, and press [OK] button to move to the user setting list.

    Concurrency (whole)
    Discharge
    direction

    Top

    OK

    Bottom

    !

    NOTE

    Discharge direction setting function may not be available on some products.

    CO2 Fan Control(general ventilator)
    A function that controls the fan when the product is turned ON/OFF, based on the CO2 concentration in the ventilation product.

    1. After selecting “CO2 fan control” in the Function settings list, press the [OK] button to go to the detail
    screen.

    2. After selecting “Fan control during operation on” or “Fan control during operation off” in the "
    CO2 Fan Control" list, you can set the following values using [<,>(left/right)] button.

    OK

    Condition 1

    Condition 2

    Operation on

    Low

    Off

    User Setting
    • You can set the product user functions.
    • Some functions may not be available in some product types.
    Menu
    Language setting
    Setpoint Type Setting
    Temperature unit setting
    Screen saver timer setting
    LCD brightness in idle setting
    External device setting
    Date setting
    Time setting
    Summer time setting
    Password setting
    Schedule initialization
    Theme setting

    Description
    Set the language to be displayed on the remote controller.
    It is the function to set GUI type on the remote controller.
    Set the temperature unit displayed on the remote controller.
    Adjust the screen Off time of the remote controller.
    Adjust the remote controller’s screen brightness.
    Set the name of external equipment and equipment logic setting
    Set the date displayed on the remote controller.
    Set the time displayed on the remote controller.
    Set the summer time in the remote controller.
    Set the password to prevent unauthorized change to remote controller settings.
    Initialize all timer settings in the remote controller.
    Set the theme of the remote controller screen.

    Humidity display

    It is the function to decide whether to display humidity on the main
    screen and additional information screen.

    Periodic
    Operation off

    Off
    Periodic

    System reboot

    Restart the remote controller.



  • Page 48

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 94

    94 USER SETTING

    USER SETTING 95

    Setpoint Type Setting

    Set the language to be displayed on the remote controller.
    • In the user setting list, select the language category, and press [OK] button to move to the detail screen.
    • After the setting, if you press [OK] button, the setting is saved and moves to the previous
    screen.

    It is the function to set GUI type on the remote controller.
    * Dual setpoint type is a function that makes it possible to set the cooling and heating target temperature simultaneously. It is recommended for customers accustomed to using North American thermostats.
    We recommend that you use it only in the region (North America).
    If select dual setpoint option, target temperature ranges will be expanded and activated override, home leave, hold mode and occupancy information based schedule.

    OK

    <Dual setpoint>

    Language
    한국어

    English

    Deutsche

    Italiano

    Français
    Español

    Русский

    Polski

    Português

    中文

    Čeština

    <Single setpoint>

    ENGLISH

    Language setting



  • Page 49

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 96

    96 USER SETTING

    USER SETTING 97

    Screen saver timer setting

    Set the temperature unit displayed on the remote controller.
    • In the user setting list, select the temperature unit setting category, and press [OK] button to
    move to the detail screen.

    Adjust the screen Off time of the remote controller.
    • Select the following setting values using [<,>(left/right)] button.

    ENGLISH

    Temperature unit setting

    Value

    OK

    15sec

    30sec (default)

    1min

    ! CAUTION
    Selecting longer stand by screen will decrease LCD lifespan.

    LCD brightness in idle setting
    Adjust the remote controller’s screen brightness.
    • Select the following setting values using [<,>(left/right)] button.

    Value

    1°C

    Celsius

    0.5°C
    Fahrenheit

    ! CAUTION
    The temperature unit function may not work or work differently in some products.
    You cannot set the temperature unit in the slave wired remote controller.

    Value
    0%

    10%
    (default)

    20%

    ! CAUTION
    Selecting brighter stand by screen will decrease LCD lifespan.

    30%



  • Page 50

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 98

    98 USER SETTING

    USER SETTING 99

    External device types

    Set the name of external equipment and equipment logic setting
    • In the user setting list, select the external device setting category, and press [OK] button to
    move to the detail screen.

    It is the function to set the name of the External device attached to the remote controller.
    • You can set the following setting values using [<,>(left/right)] button.

    OK
    Value
    Motor Lighting

    External device use
    • In the external device setting list, select “External device use” category, and press [OK] button
    to move to the external device use setting screen.
    - If external device use setting value is use, you can see the control unit of external device in
    main screen.

    Value
    Not use

    Use

    Fan

    Heater

    Pump

    Others

    ENGLISH

    External device setting



  • Page 51

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 100

    100 USER SETTING

    USER SETTING 101

    Date setting

    It is the function to set to use the information managed by the wired remote controller as the
    contact point control condition to widen the usage of the contact point (Digital Output) installed in
    the remote controller.

    Set the date displayed on the remote controller.
    • In the user setting list, select the date category, and press [OK] button to move to the detail
    screen.
    • After the setting, if you press [OK] button, the setting is saved and moves to the previous
    screen.

    • In the external device setting list, select the On/Off condition setting category, and press [OK]
    button to move to the detail screen.

    OK

    OK

    Condition 1

    Condition 2

    Condition 3

    Condition 4

    None

    Deactivate

    -

    Deactivate

    On

    -

    Aircon

    Cool mode

    -

    Heat mode

    -

    Fan mode

    -

    Dry mode

    -

    Auto mode

    -

    External device name On
    External device name Off

    Over

    Current Temp.

    1°C~ 39.5°C

    Occupied

    -

    -

    Unoccupied

    -

    -

    Under

    • The External device operates as the operation set in the conditions 1~3.
    • If the External device is set to auto while both ON condition and OFF condition are not set, contact point OFF is output.
    • If the ON condition and OFF condition are the same, it is finally processed as OFF condition.

    ENGLISH

    On condition / Off condition



  • Page 52

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 102

    102 USER SETTING

    USER SETTING 103

    Summer time setting

    Set the time displayed on the remote controller.
    • In the user setting list, select the time category, and press [OK] button to move to the detail
    screen.
    • After the setting, if you press [OK] button, the setting is saved and moves to the previous
    screen.

    Set the daylight savings time dates in the remote controller.
    • In the user setting list, select the summer time setting category, and press [OK] button to
    move to the detail screen.
    - Summer time: The system to advance the time by 1 hour from the spring when the day is
    longer and return back in the fall when the day gets shorter.
    - When it becomes AM 02:00 on the DST start date, the current time changes to AM 03:00,
    and when it becomes AM 02:00 of the DST end date, the current time changes to AM 01:00.

    OK
    OK

    ENGLISH

    Time setting



  • Page 53

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 104

    104 USER SETTING

    USER SETTING 105

    Schedule initialization

    Set the password to prevent unauthorized change to remote controller settings.
    • Select the user password setting category, and press [OK] button to move to the detail screen.
    - If the password is set, when you enter “menu – setting”, you need to input password to
    enter the setting list.
    - When you forgot the password, you can initialize the password using the installer setting’s
    “password initialization”.
    The initialized password is “0000”.

    Initialize all timer settings in the remote controller.
    • In the user setting list, select the schedule initialization setting category, and press [OK] button
    to move to the detail screen.
    - Press the check button to initialize the sleep/simple timer, on/off timer, schedule and exception date in the remote controller.

    OK
    OK

    ENGLISH

    Password setting



  • Page 54

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 106

    106 USER SETTING

    USER SETTING 107

    Humidity display

    Set the theme of the remote controller screen.
    • Select either white or black using [<,>(left/right)] button.

    It is the function to decide whether to display humidity on the main screen and additional information screen.
    You can use [<, > (left/right)] button to set the setting values (On or Off).

    ON

    Display humidity.

    OFF

    Do not display humidity.

    Setting value

    !

    NOTE

    If humidity display is `ON`, the displayed humidity is different according to the humidity
    detection location setting (installer setting).
    • Remote controller: remote controller humidity display.
    • Indoor unit: If it receives indoor unit humidity, it displays the indoor unit humidity, and if it
    does not receive indoor unit humidity, it does not display humidity.

    ENGLISH

    Theme setting



  • Page 55

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 108

    108 USER SETTING

    SERVICE SETTING 109
    ENGLISH

    System restart

    SERVICE SETTING

    Restart the remote controller.
    • In the user setting list, select the system restart setting category, and press [OK] button to
    move to the detail screen.
    - In the detail screen, when you press [OK] button, a popup message is displayed, press the
    check button, to restart the system.
    - For forced reset, press down [On/Off + Back] button for 5 seconds to restart the system.

    How to enter service setting
    To enter the menu displayed at the bottom, you need to enter the service setting menu as follows.
    • In the menu screen, press [<,>(left/right)] button to select the setting category, and press [OK]
    button to move to the setting list.
    • In the setting list, select the service setting category, and press [OK] button to move to the
    service setting list.

    OK

    OK

    Service setting
    • You can set the product service functions.
    • Some functions may not be displayed/operated in some product types.
    Menu

    Description

    Service contact

    Check and input the service center phone number that you can call
    when there is service issue.

    Model Information

    Check the indoor/outdoor product group and capacity information to
    which the remote controller is connected.

    RMC Version Information
    Error History
    Open Source License

    Check the remote controller model name and software version.
    View the connected indoor unit’s error history.
    View the remote controller’s open source license.



  • Page 56

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 110

    110 SERVICE SETTING

    SERVICE SETTING 111

    Model information

    Check and input the service center phone number that you can call when there is service issue.
    • In the service setting list, select the service contact point and press [OK] button to move to the
    detail screen.
    • While “edit” button is selected, press [OK] button to move to the edit screen, change it, and
    press [OK] button to change the service contact point.

    Check the indoor/outdoor product group and capacity information to which the remote controller
    is connected.
    • In the service setting list, select the indoor/outdoor model information category, and press [OK]
    button to move to the detail screen.
    • Indoor unit capacity
    - 1kWh = 1kBtu * 0.29307
    kWh is the result calculated based on Btu, There may be a small difference between calculated and actual capacity.
    Ex) If the indoor unit capacity is 18kBtu, it is displayed as 5kWh.

    OK
    OK

    OK

    ENGLISH

    Service contact



  • Page 57

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 112

    112 SERVICE SETTING

    SERVICE SETTING 113

    Error history

    Check the indoor/outdoor product group and capacity information to which the remote controller
    is connected.
    • In the service setting list, select the remote controller version information check category, and
    press [OK] button to move to the detail screen.

    View the connected indoor unit’s error history.
    • In the service setting list, select ‘check error history’ category, and press [OK] button to move
    to the detail screen.
    - You can view up to 20 error instances sorted by date occurred.

    OK

    OK

    ENGLISH

    RMC Version Information



  • Page 58

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 114

    114 SERVICE SETTING

    INSTALLATION 115
    ENGLISH

    Open source license

    INSTALLATION

    View the remote controller’s open source license.
    • In the service setting list, select the open source license category, and press [OK] button to
    move to the detail screen.

    Installation of Remote Controller
    • After fixing the remote controller installation plate on the desired location, fix it firmly with the
    provided screws.
    - If the installation plate is not flat on the surface, it may result in the controller being twisted
    and cause a defect.
    - If there is a mounting box, install the remote controller installation plate using the fixings holes
    which suit, as in the below diagrams.
    - Do not leave a gap with the wall or product loose after the installation.

    OK
    • The wired remote controller cable can be installed in 3 directions. Install to the suitable
    direction according to the installation environment.
    - Installation direction: Rear entry, top side, right side
    - When you install the remote controller cable at the top side and right side, remove the remote
    controller cable guide hole before the installation.
    ※ Use a long nose pliers to remove the guide hole.
    • After removing the hole, trim the cut surface neatly.
    ‫ ڹ‬Top side guide groove
    ‫ ڹ‬Top side guide groove
    ‫ں‬Right side guide
    groove
    ‫ں‬Right side guide
    groove

    ‫ڸ‬Rear cable entry

    • After fixing the remote controller top side on the installation plate attached to the wall as in the
    following figure, press the bottom side to combine with the installation plate.
    - Do not leave a gap in the top, bottom, left, and right side of the remote controller and the installation plate after combining them.
    - Before combining with the installation plate, arrange the cables to avoid interference with the
    circuit parts.
    <Order of Combining>

    Wall

    Wall



  • Page 59

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 116

    116 INSTALLATION

    INSTALLATION 117
    ENGLISH

    • When you remove the remote controller from the installation plate, insert a small flat head
    screwdriver into the bottom side separation hole and turn clockwise to separate the remote
    controller.
    - There are 2 separation holes at the bottom part. Slowly separate one by one.
    - Be careful not to damage the internal parts during the removal.

    Group control
    • It connects and controls 2 or more air conditioner indoor units to one wired remote controller.
    ※Connect using the group control cable.
    Indoor unit Main PCB
    Indoor unit 2
    Slave

    Indoor unit 1
    Master

    <Order of Separation>

    Wall Side

    RED(12V)
    YELLOW(SIG)
    BLACK(GND)

    YELLOW(SIG)
    BLACK(GND)

    Indoor unit 3
    Slave
    YELLOW(SIG)
    BLACK(GND)

    OK

    ① Group control cable (PZCWRCG3): Connect to indoor unit’s wired remote controller connector
    ② Extension cable (PZCWRC1): Connect to No. ① cable and slave indoor unit’s wired remote
    controller connector

    • Use the connection cables to connect the indoor unit with the remote controller.

    While No. ① cable is connected, connect No. ② cable.
    DC 12 V

    Red

    Signal

    Yellow

    GND

    Black

    Please check if connector is normally connected.

    1
    Indoor
    Unit side

    OK

    Connecting cable

    • For the following cases, separately purchase and use the cables suitable for the situation.
    - Do not install the cable over 50 m. (It may cause communication issues.)
    - If the distance between the wired remote controller and the indoor unit is 10 m or more : 10
    m extension cable (model name: PZCWRC1)
    - If you control several indoor unit products with one wired remote controller : Group control
    cable (model name: PZCWRCG3)

    !

    NOTE

    During the wired remote controller installation, do not bury it in the wall. (It may cause
    temperature sensor failure.)
    Do not install the cable over 50 m. (It may cause communication defect.)
    When you install the extension cable, carefully check the direction of the connectors on the
    remote controller side and the product side before the installation.
    Specification of extension cable: AWG 24, 3 conductor or above.

    !

    2

    NOTE

    • Connect only GND and signal cable to the indoor unit set as slave. (If power cable is also
    connected, it may cause loss of communication)
    • Inquiries related to the purchase of the cable shall be directed to the specialized company
    and the service center.
    • After checking the existence of the event communication in the product manual, change
    master/slave of the remote controller.
    ※For details, refer to ‘remote controller master/slave’ contents.
    • Change master/slave of the indoor unit.
    - For ceiling cassette and duct product group, change the setting with the indoor unit PCB
    switch.
    Master

    GND
    Signal cable
    12V

    Slave

    Slave

    No. 3 switch OFF: master (factory ship-out based)
    Black

    Yellow
    Red
    No. 3 switch ON: slave
    GND Signal cable
    OK



  • Page 60

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 118

    118 INSTALLATION

    - After completing the master/slave setting in the indoor unit product, turn Off the power of the
    indoor unit product, and turn On the power after 1 minute.

    !

    NOTE

    • During the group control, set only 1 indoor unit as master.
    • During the group control, some functions other than the basic operation setting, fan speed
    Low/Med/High, remote controller lock setting, and time setting may be limited.
    • During the individual control, if the master indoor unit Dip switch is set to slave, malfunction
    may occur.

    INSTALLATION METHOD TO USE EXTERNAL
    DEVICE
    Cable connection method to use external device
    1) Wired remote controller-cable connection method.
    - In the wired remote controller, connect the part marked in the following figure (J02C, DOPort) to the cable.
    - According to the installation environment, there are 3 directions (Rear entry, top side, and
    right side) for the installation.
    2) Cable extension connection method
    - Among the cables connected to the wired remote controller, cut the remaining connectors
    on the other side, and then extend and connect the cables
    - Extension cable specification: 24~26AWG.

    ! CAUTION
    For the External device connection, use the cable insulated with sheath for the extension connection.
    Before combining with the installation plate, arrange the cables to avoid interference with the internal parts.
    RMC
    DO-Port

    30cm

    2

    (GND_Black)

    3

    (DC 12 V_Red)

    Remote
    controller
    product
    composition

    • Output specification
    - Voltage : DC 11~12V
    - Current : 5mA

    Field connection

    ENGLISH

    - For the details on the wireless remote controller master/slave setting changes, refer to the
    wireless remote controller manual.

    INSTALLATION METHOD TO USE EXTERNAL DEVICE 119



  • Page 61

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 120

    120 AIR CONDITIONER AND VENTILATION INTERFACE

    INSTALLER SETTING 121

    • It controls using the wired remote controller at a place where the air conditioner indoor unit and
    the ventilation product are connected and installed at the same time.
    - When the power is applied, the remote controller recognizes the product and operates normally.
    Independent operation

    Interfaced operation

    [general ventilation
    independent operation]

    [General ventilation interfaced operation]

    General
    ventilation

    General
    ventilation

    OK

    WIRED
    REMOTE
    CONTROLLER

    [Direct ventilation
    independent operation]

    Air conditioner
    indoor unit

    OK

    WIRED
    REMOTE
    CONTROLLER

    INSTALLER SETTING
    How to enter installer setting
    ! CAUTION
    The installer setting mode is the mode to set the remote controller’s detail function. If the installer setting mode is incorrectly set, it may cause product failure, user’s injury, or property damage. It must be set by the installation specialist with the installation license, and if it is installed or
    changed without installation license, all problems caused will be the responsibility of the installer,
    and may void the LG warrenty.
    • In the menu screen, press [<,>(left/right)] button to select the setting category, and press
    [∧(up)] button for 3 seconds to enter the password input screen for the installer setting.
    • Input the password and press [OK] button to move to the installer setting list.

    WIRED
    REMOTE
    CONTROLLER

    OK

    [Direct ventilation interfaced operation]

    General
    ventilation

    Direct
    ventilation

    General
    ventilation

    ENGLISH

    AIR CONDITIONER AND VENTILATION INTERFACE

    Air conditioner
    indoor unit

    OK

    General
    ventilation

    WIRED
    REMOTE
    CONTROLLER

    ※The wiring method is the same as the air conditioner user manual. (Refer to the remote controller manual group control page contents)
    ※Ventilation product means general ventilation product and direct cooling type ventilation product.

    OK

    OK

    ※Installer setting password
    Main screen → menu → setting → service → RMC version information → SW Version
    Example) SW version : 1.00.1 a
    In the above case, the password is 1001.

    !

    NOTE

    Some categories of the installer setting menu may not be available depending on the
    product function or the menu name may be different.



  • Page 62

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 122

    122 INSTALLER SETTING

    INSTALLER SETTING 123

    • You can set the product user functions.
    • Some functions may not be displayed/operated in some product types.
    Menu

    Description

    Test run setting

    It is the function to set the trial operation at the initial product installation.

    Central control address
    Setting

    It is the function to set the central control address of the indoor unit
    during the central controller connection.

    ESP setting

    It is the function to set the wind amount value corresponding to each
    wind amount for easy installation.

    Temperature sensor setting

    It is the function to select the temperature sensor that will decide the
    indoor temperature.

    Ceiling height setting

    It is the function to control the wind amount stage according to the
    ceiling height for the ceiling type products.

    Static pressure setting

    The fixed pressure setting can be set only in the duct products.
    It cannot be set in other products.

    RMC master/slave setting

    Override master/slave setting

    Menu

    Description

    Guard timer

    It is a function that sets the minimum running time of outdoor unit
    cycle mode when switching from cooling mode to heating mode and
    vice versa during Auto Operation mode.

    Fan speed in Cooling thermal It is a function that sets the indoor unit fan movement, in cooling
    off
    mode, when thermal is off.
    Primary heater setting

    It is the function to set the heater usage to have higher priority over
    the outdoor unit cycle during the indoor unit heating operation.

    Air conditioner Fan operation It is the function to set whether to operate the air conditioner fan durinterlocked with ventilation ing the interface operation of the air conditioner and the ventilation
    setting
    product.
    Indoor unit Auto-Start
    setting

    It is a function that sets whether to restore the indoor unit operation
    by resuming the previous power-on state or as power-off state in the
    power failure compensation.

    Occupancy duration time
    setting

    It is the function to set the occupied decision maintaining time among
    the occupied sensor values.

    It is the function to set group control or 2-remote controller control.

    CN_CC setting

    The operation master / slave selection function is to avoid other mode
    operations, and it is the function to prevent the selection of the opposite mode of the indoor unit set as master by the indoor units set as
    slaves.

    It is the function to set whether to install (use) Dry Contact.
    (It is not a function for Dry Contact installation, but it is a function to
    set the usage of the indoor unit’s CN_CC port.)

    CN_EXT setting

    It is the function to set the indoor unit’s Dry Contact Port to control external input and output according to DI/DO set by the customer. (It is
    the function to decide the usage of the contact point port (CN_EXT)
    mounted in the indoor unit PCB.)

    Dry contact mode setting

    Dry contact function is the function that can be used only when the
    dry contact devices is separately purchased and installed.

    Fixed air volume

    It is the function to apply different fan speeds automatically for each
    thermal control status.

    Zone Type Setting

    It is possible to setup zone new type or old one of the product which
    is available to install the damper controller.

    Zone Number Setting

    Zone Number is to set the number of installed zones. It's possible to
    control only in zone new type.

    Emergency Heater setting

    It is the function to set whether to use emergency heater control function and the usage environment.

    Func. control during grp.
    Control setting

    It is the function to set common functions or some functions to be
    controlled by the master indoor unit standard during the group control.

    Option Kit – Plasma / Heater /
    Humidification / Elevation grill
    / Ventilation / Refrigerant leakage detection sensor

    It is the function to set whether to mount option unit (Plasma / Humidification / Heater / Ventilation / Elevation grill / Aux Heater / Refrigerant
    leakage detection sensor) when it is additionally installed or removed
    after the mass production.

    Expand of Temperature Range

    This function is used for select setting temperature range option.

    Indoor unit address verification

    This function allows you to check the address of the indoor unit designated by the outdoor unit.

    Static pressure step setting

    This is the function that static pressure of the product is divided in 11
    steps for setting.

    ODU function master setting It is the function to set the outdoor unit’s function Master / Slave.

    Fan continuous operation
    setting

    It is the function to set the indoor unit’s continued Fan function usage.
    It is the function to maximize the cooling/heating efficiency by the outdoor unit operating the indoor unit fan operation longer than the previous operation method.

    Low noise mode priority
    setting

    It is the function to set the main agent of the low noise mode control.
    (It is the function to set only one of the outdoor unit / remote controller can control the low noise operation.)

    Human detection sensor set- It is the function to set whether to install human detection sensor and
    ting
    operation standard value.
    Humidity sensing position
    ODU cycle priority

    It is the function to set the location to detect humidity.
    This function can select standby mode or priority cooling.

    Outdoor temp. for heating
    stages

    This function can select outdoor temperature values for use reference
    point of heater and heating mode operation.

    Estimated energy display
    CN_PTC setting

    This function can set to display energy data which ODU estimated.
    This is a function to set PTC Port of indoor unit.

    Password initialization

    It is the function to initialize (0000) the password when you forgot the
    password set in the remote controller.

    ENGLISH

    Installer setting – air conditioner



  • Page 63

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 124

    124 INSTALLER SETTING

    INSTALLER SETTING 125

    Test run setting (air conditioner / DX ventilator)

    • You can set the product user functions.
    • Some functions may not be displayed/operated in some product types.

    After product installation, the Test run must be performed. For Test run related details, refer to
    the product manual.
    • In the installer setting list, select the Test run setting category, and press [OK] button to move
    to the detail screen.
    - You can select ‘cooling Test run / heating Test run’
    - During the Test run, if you start the following functions, the Test run stops.
    ☞ Operation mode, desired temperature, fan speed, wind direction, start/stop

    Menu
    Test run setting
    Central control address Setting

    Applied products

    Description

    DX(Direct Exchanger) Type It is the function to set the trial operation at the initial product installation.
    General

    Air supply ESP
    General/DX Type
    Air discharge ESP

    It is the function to set the central control address of the indoor unit during
    the central controller connection.
    It is the function to set the fan speed value corresponding to the air supply
    side fan speed.
    It is the function to set the fan speed value corresponding to the air discharge side fan speed.

    Temperature sensor setting

    DX Type

    It is the function to select the temperature sensor that will decide the indoor
    temperature.

    Product direction

    General

    It is the function to set the ventilation indoor unit’s installation direction.

    Express ventilation priority
    General/DX Type
    RMC master/slave setting

    It is the function to set the priority of the air supply and discharge during the
    express ventilation operation.
    It is the function to set group control or 2-remote controller control.

    DX Type

    The operation master / slave selection function is to avoid other mode operations, and it is the function to prevent the selection of the opposite mode
    of the indoor unit set as master by the indoor units set as slaves.

    Dry contact mode setting

    DX Type

    Dry contact function is the function that can be used only when the dry contact devices is separately purchased and installed.

    Fixed fan speed setting

    DX Type

    It is the function to set the indoor unit’s fan speed option to variable or fixed.

    Hum. Of Stand-alone Vent.
    Mode

    General/DX Type

    It is the function to set whether to use the humidification function in the direct cooling type ventilation’s ventilation single operation.

    Hum. Of Vent. With Heating
    Oper.

    DX Type

    It is the function to set the direct cooling type ventilation’s heating humidification function as auto or manual.

    Vent. Fan Speed Alignment

    General

    It is the function to increase/decrease ventilation’s standard fan speed from
    the current status according to the field environment.

    Indoor unit address verification

    DX Type

    This function allows you to check the address of the indoor unit designated
    by the outdoor unit.

    Indoor unit Auto-Start setting

    DX Type

    It is a function that sets whether to restore the indoor unit operation by resuming the previous power-on state or as power-off state in the power failure compensation.

    CN_EXT setting

    DX Type

    It is the function to set the indoor unit’s Dry Contact Port to control external input
    and output according to DI/DO set by the customer. (It is the function to decide the
    usage of the contact point port (CN_EXT) mounted in the indoor unit PCB.)

    ODU function master setting

    DX Type

    It is the function to set the outdoor unit’s function Master / Slave.

    Low noise mode priority setting

    DX Type

    It is the function to set the main agent of the low noise mode control. (It is
    the function to set only one of the outdoor unit / remote controller can control the low noise operation.)

    Filter check alarm

    General

    This function sets the filter check alarm of the ventilation product.

    Override master/slave setting

    OK

    ENGLISH

    Installer setting - ventilator



  • Page 64

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 126

    126 INSTALLER SETTING

    INSTALLER SETTING 127

    ESP setting (air conditioner / general, DX ventilator)
    It is the function to set the fan speed value corresponding to each fan speed for easy installation.

    It is the function to set the central control address of the indoor unit to allow communication with
    a central controller,
    • In the installer setting list, select the central control address setting category, and press [OK]
    button to move to the detail screen.
    - Select a hex value between 00 and FF.
    Value 1: group address setting / value 2: indoor unit address setting

    OK

    !

    NOTE

    If ESP is incorrectly set, the air conditioner may malfunction.
    This function must be set by the installation specialist that holds an installation license.
    For ventilation products, separate ESP values are used for the supply and exhaust fans.

    OK

    • In the installer setting list, select the ESP setting category, and press [OK] button to move to
    the detail screen.
    Product

    ESP fan speed

    value

    Slow
    Low
    Air conditioner

    Med
    High
    Power

    0 ~ 255

    Low
    Ventilation

    High
    Power

    !

    NOTE

    Be especially careful not to switch ESP values corresponding to each fan speed.
    Engineering manuals have ESP setting tables that reference air flow and corresponding
    value setting to achieve the flow.
    The ESP values that can be set may be different for each product and capacity.

    ENGLISH

    Central control address setting (air conditioner / general, DX
    ventilator)



  • Page 65

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 128

    128 INSTALLER SETTING

    INSTALLER SETTING 129

    Ceiling height setting (air conditioner)
    It is the function to control the fan speed stage according to the ceiling height in the ceiling type
    product.
    • You can set the following setting values using [<,>(left/right)] button.

    Temperature sensor location

    Description

    Remote controller

    Operate the system with wired remote controller’s temperature
    sensor

    Indoor Unit

    Ceiling height
    Low

    Operate the system with indoor unit’s temperature sensor
    Cool

    2TH
    Heat

    Standard

    Compare the temperatures of the indoor unit and the wired remote controller and operate with the higher temperature
    (There are system operated with lower temperature)
    Compare the temperatures of the indoor unit and the wired remote controller and operate with the lower temperature

    • 2TH function’s operation characteristics may be different for each product.

    !

    Description
    Fan speed operates one step slower than the default value.
    Operates at the default fan speed

    High

    Fan speed operates one step faster than the default value.

    Very high

    Fan speed operates two steps faster than the default value.

    NOTE

    When group control is enabled some functions are limited depending on product type.

    ENGLISH

    Temperature sensor(2TH) setting (air conditioner / DX ventilator)
    It is the function to select the temperature sensor to decide the indoor temperature.
    • You can set the following setting values using [<,>(left/right)] button.



  • Page 66

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 130

    130 INSTALLER SETTING

    INSTALLER SETTING 131

    Static pressure setting can be set only in the duct products. (It cannot be set in other products.)
    • You can set the following setting values using [<,>(left/right)] button.

    Remote controller master / slave setting
    (air conditioner / General, DX ventilator)
    This function sets configuration for the master/slave setting through the remote controller.
    • Change setting values using [<,>(left/right)] button.

    Description
    Static pressure
    Variable high static pressure

    V-H

    Variable / Fixed

    ESP default value

    M/S

    Variable

    High static pressure(High)

    Master (default)

    Using group control, the indoor units are operated based on the remote controller.

    Slave

    Using group control, all remote controllers except 1 master remote
    controller are set as slaves.

    Fixed high static pressure

    F-H

    Fixed

    High static pressure(High)

    Variable low static pressure

    V-L

    Variable

    Low static pressure(Low)

    Fixed low static pressure

    F-L

    Fixed

    Low static pressure(Low)

    • 2TH function’s operation characteristics may be different for each product.

    Description

    • 2TH function’s operation characteristics may be different for each product.

    ENGLISH

    Static pressure setting(air conditioner)



  • Page 67

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 132

    132 INSTALLER SETTING

    INSTALLER SETTING 133

    The operation master / slave selection function is to avoid other mode operations, and it is the
    function to prevent the selection of opposite mode of the indoor unit master by the indoor units
    set as slaves.
    • Change setting values using [<,>(left/right)] button.

    Dry contact mode setting (air conditioner / DX ventilator)
    Dry contact function is the function that can be used only when the dry contact devices is separately purchased and installed.
    • Change setting values using [<,>(left/right)] button.

    Value
    Auto
    M/S
    Master

    Slave

    !

    Description

    manual

    Using group control, this master sets the mode of slave IDU’s.
    For the indoor unit set as slave, it can only select the some operation
    mode of the master indoor unit cycle.
    Ex) Master is in cooling cycle, Slave can select cooling, dehumidification, auto, and wind only
    Master is in heating cycle, Slave can select auto, heating, and wind
    only

    NOTE

    Override M/S setting function is only available in some products.

    !

    NOTE

    For dry contact mode related detail functions, refer to the individual dry contact manual.
    What is dry contact?
    It means the contact point signal input when the hotel card key, human body detection
    sensor, etc. are interfacing with the air conditioner.
    Added system functionality by using external inputs (dry contacts and wet contacts).

    ENGLISH

    Override Master/Slave setting (air conditioner / General, DX
    ventilator)



  • Page 68

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 134

    134 INSTALLER SETTING

    INSTALLER SETTING 135

    Zone Type Setting(air conditioner)

    It is the function to apply different fan speeds automatically for each thermal control status.
    • You can set the following setting values using [<,>(left/right)] button.

    This function is only available on some products.
    This function select a type of zone control type which indoor unit support as 'new type' or 'old
    type'.

    Value

    Comp on

    Comp off

    Variable

    Set fan speed

    Low

    Fixed

    Set fan speed

    Set fan speed

    Value
    Old
    New(4 Zone)
    New(8 Zone)

    Zone Number Setting(air conditioner)
    This function is only available on some products.
    Zone Number is to set the number of installed zones. It's possible to control only in zone new
    type.

    Value
    New(4 zone) : 2~4
    New(8 zone) : 2~8

    ENGLISH

    Fixed air volume (air conditioner / DX ventilator)



  • Page 69

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 136

    136 INSTALLER SETTING

    INSTALLER SETTING 137

    Function control during group Control setting (air conditioner)

    Enable the emergency heater control function and the usage environment.
    • In the installer setting list, select the emergency heater setting category, and press [OK] button
    to move to the detail screen.
    - In case of an error, it sets whether the emergency heater can be used / outdoor temperature
    standard heater operation usage setting and temperature step value setting / and during the
    emergency heater operation, whether to use the indoor unit fan operation.

    This function enables the control of the common functions or some functions based on the master indoor unit during the group control.
    • Change setting values using [<,>(left/right)] button.

    OK

    !

    Value

    Description

    Not use

    Common function,

    Use

    Use expanded function which
    is based on master indoor unit

    NOTE

    Common functions and some indoor unit master standard setting shall be set only during
    the group control with the same type indoor units.
    During the group control with different indoor unit types, set it as ‘000’ to use the existing
    group control method.

    Value

    Outdoor temperature standard heater
    operation

    Fan operation in emergency
    control

    Not use

    -

    -

    Use

    !

    Emergency heater

    Step 0 ~ 3

    Extended emergency heater

    Step 0 ~ 15

    On/Off

    NOTE

    This function setting must be carried out by a certified-technician.

    ENGLISH

    Emergency heater setting (air conditioner)



  • Page 70

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 138

    138 INSTALLER SETTING

    INSTALLER SETTING 139

    Expand of Temperature Range (air conditioner)

    At the Code field, select when air cleaner/heater/humidifier/elevation grill/ventilation KIT/Aux
    Heater/refrigerant leakage detection sensor are newly installed to the indoor unit or when an installed KIT is removed.
    • You can set the following setting values using [<,>(left/right)] button.

    This function using in dual setpoint control mode.
    This function is used for select setting temperature range option.

    Value
    Function

    Clear : 60~86 °F / 16~30 °C (default)

    Value

    Set : 40~99 °F / 4~37.5 °C

    Plasma purification
    Heater

    !

    Humidifier
    Elevation grill
    Ventilation Kit
    Aux Heater
    Refrigerant leakage detection sensor

    Not install / Install

    NOTE

    When the set values are changed, the items below will be initialized.
    - Target temperature (default: Cooling: 86 °F(30 °C)/ Heating: 60 °F(16 °C))
    'home leave' temperature (default: Cooling: 86 °F(30 °C)/ Heating: 60 °F(16 °C))
    In case of the setting expanded temperature range (set), please note that the setting of the
    wired remote controller can be altered under below circumstances.
    - In case of cooling at 30~37.5 °C(64~99 °F), it is changed to cooling at 86 °F(30 °C).
    - In case of heating at 4~15.5 °C(40~86 °F), it is changed to heating at 60 °F(16 °C).
    - If set on dual setpoint, it is changed to the current operation mode(cooling or heating) of
    the indoor unit.
    Situation where changes in the setting occur
    a. Operates the Auto address work and pipe search in situations such as product installment
    and service.
    b. Occurrence of errors and deactivation.
    c. Command generated by the central control, outdoor unit, Dry contact, Remote controller,
    indoor unit switch.

    ENGLISH

    External devices of indoor unit setting (air conditioner)



  • Page 71

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 140

    140 INSTALLER SETTING

    INSTALLER SETTING 141

    Static pressure step setting (air conditioner)

    This function allows you to check the address of the indoor unit designated by the outdoor unit.
    • In the installer setting list, select the indoor unit address check category, and press [OK] button
    to move to the detail screen.

    It is the function to subdivide and set the product’s Static pressure to 11 stages.
    • Change setting values using [<,>(left/right)] button.

    OK

    Value
    Step 0 ~ Step 11

    !

    NOTE

    If Static pressure step setting is used, the Static pressure setting is not used.
    For the Static pressure step value for each stage, refer to the indoor unit product manual

    ENGLISH

    Indoor unit address verification (air conditioner / DX ventilator)



  • Page 72

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 142

    142 INSTALLER SETTING

    INSTALLER SETTING 143

    Fan speed in Cooling thermal off (air conditioner)

    It is a function that sets the minimum running time of outdoor unit cycle mode when switching
    from cooling mode to heating mode and vice versa during Auto Operation mode.
    Under the condition of cooling/heating switching, it switches between cooling and heating mode
    after operation during the time scheduled in the Guard timer.

    Indoor unit fan, in cooling mode, during thermal off condition.
    • Select value using [<,>(left/right)] button.

    Value
    Step

    Value

    Low

    0

    0 minute

    Off

    Fan speed low
    Fan off

    1

    15 minutes

    Setting

    fan speed setting value

    2

    30 minutes

    3

    45 minutes

    4

    60 minutes

    ENGLISH

    Guard timer(air conditioner)



  • Page 73

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 144

    144 INSTALLER SETTING

    INSTALLER SETTING 145

    It is the function to set the air conditioner fan operation if the ventilation is operated while the air
    conditioner operation is stopped when the air conditioner and the ventilation are installed to interface with each other.
    • You can set the following setting values using [<,>(left/right)] button.

    Value
    Not use
    Use

    Air conditioner Fan operation interlocked with ventilation setting
    (air conditioner)
    It is the function to set the air conditioner fan operation if the ventilation is operated while the air
    conditioner operation is stopped when the air conditioner and the ventilation are installed to interface with each other.
    • You can set the following setting values using [<,>(left/right)] button.

    Description
    During the heating, heater is set to be used as secondary
    During the heating, heater is set to be used as main

    Value

    Description

    Off

    The air conditioner indoor unit Fan is Off during the ventilation interface

    On

    The air conditioner indoor unit operates in very weak wind during the ventilation interface

    - When the air conditioner operation is Off, if the ventilation product is in operation, the air conditioner fan shall be operated, and when the fan is in operation, dust may fall, so it is the function
    to set the air conditioner fan operation status in case of ventilation interface through the setting.

    ENGLISH

    Primary heater setting(air conditioner)



  • Page 74

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 146

    146 INSTALLER SETTING

    INSTALLER SETTING 147

    Occupancy duration time setting(air conditioner)

    It is a function that sets whether to restore the indoor unit operation by resuming the previous
    power-on state or as power-off state in the power failure compensation.
    • You can set the following setting values using [<,>(left/right)] button.

    It is a function that sets the light-on/occupancy duration after motion is detected when installing
    an occupancy sensor.
    • You can set the following setting values using [<,>(left/right)] button.

    Value
    Use
    Not use

    Description
    Use indoor unit auto restart
    Not use indoor unit auto restart

    Value
    0 Minute
    10 Minutes
    30 Minutes
    60 Minutes

    ENGLISH

    Indoor unit Auto-Start setting (air conditioner / DX ventilator)



  • Page 75

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 148

    148 INSTALLER SETTING

    INSTALLER SETTING 149

    CN_EXT setting (air conditioner / DX ventilator)

    It is the function to set the usage of the indoor unit’s CN_CC port.
    • Select CN_CC setting category, and press [OK] button to move to the detail screen.

    It is the function to set to control the external input and output according to DI/DO set by the customer using the indoor unit’s Dry Contact Port. (It is the function to decide the usage of the contact point port (CN_EXT) mounted in the indoor unit PCB.)
    • In the installer setting list, select CN_EXT setting category, and press [OK] button to move to
    the detail screen.

    OK
    OK

    Value

    Description

    DC auto install
    (default)

    When power is applied to the product, indoor unit when the contact
    point is on in Dry Contact installed state recognizes Dry Contact installation

    DC manual not install
    DC manual install

    Do not use (install) Dry Contact
    Use (install) Dry Contact

    Programmable DI/DO Use as Programmable DI/DO (Simple On/Off)

    !

    NOTE

    CN_CC is the device connected to the indoor unit to recognize and control the external
    contact point.

    Value

    Description

    Not use
    (default)

    Use installer code No. 41 setting value (simple Dry Contact setting
    value)

    Simple operation
    control

    Simple operation On/Off

    Single emergency stop

    Indoor unit single emergency stop

    Occupied / Unoccupied

    Occupied / Unoccupied

    All emergency stop

    Indoor unit all emergency stop
    ※It can be set only when there is indoor unit emergency stop
    function.

    ENGLISH

    CN_CC setting (air conditioner)



  • Page 76

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 150

    150 INSTALLER SETTING

    INSTALLER SETTING 151

    It is the function to set the outdoor unit’s function Master / Slave.
    • You can set the following setting values using [<,>(left/right)] button.

    Value

    Slave

    Master

    Description
    Cannot enter the Smart load control function setting
    Cannot enter the low noise operation time setting
    Cannot enter the refrigerant noise reduction setting
    Cannot enter the defrost mode setting
    Smart load control function setting is possible
    Low noise operation time setting is possible
    Refrigerant noise reduction setting is possible
    Low noise operation control main agent setting is possible
    Defrost mode setting is possible

    ! CAUTION
    ※When you change the outdoor unit function master setting from master to slave, check the operation status of the outdoor unit function (outdoor unit low noise operation, smart load control)
    and make sure to stop the outdoor unit function before the change.

    Fan continuous operation setting (air conditioner)
    It is the function to set the indoor unit’s continued fan function usage. (It is the function to maximize the cooling/heating efficiency by the outdoor unit operating the indoor unit fan operation
    longer than the previous operation method.)
    • You can set the following setting values using [<,>(left/right)] button.

    Value
    Clear
    Set

    Description
    Do not use continued fan usage
    Use continued fan usage

    ENGLISH

    Outdoor unit function master setting (air conditioner / DX ventilator)



  • Page 77

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 152

    152 INSTALLER SETTING

    INSTALLER SETTING 153

    Human detection sensor (air conditioner)

    It is the function to set the low noise mode control main agent. (It is the function to set that only
    one of the outdoor unit / remote controller can control the low noise operation.)
    • You can set the following setting values using [<,>(left/right)] button.

    It is the function to set whether to install human detection sensor and operation standard value.
    • In the installer setting list, after selecting human detection sensor setting category, if you press
    [OK] button, it moves to the detail screen.

    Value

    Description

    RMC

    Ignore the outdoor unit PCB’s low noise operation Switch Setting value
    - Function setting – remote controller low noise operation time menu deactivation

    ODU(default)

    It is controlled in the outdoor unit itself according to the outdoor unit
    PCB’s low noise operation Switch Setting value
    - Function setting – remote controller low noise operation time menu deactivation

    • You can set the following setting values for each category using [<,> (left/right)] button.

    Value

    Description

    Installation status

    Not installed, basic installation, 90º rotation installation

    Detection result sending cycle

    5 s, 30 s, 1 min., 3 min.

    Sensitivity setting

    Standard, low sensitivity, high sensitivity

    Temperature control option

    Step 0 : Keeps the product running and uses the temperature power saving function.
    Step 1 : The operation of indoor units is stopped by
    using the temperature power saving function.

    ENGLISH

    Low Noise Mode Priority setting (air conditioner / DX ventilator)



  • Page 78

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 154

    154 INSTALLER SETTING

    INSTALLER SETTING 155

    ODU cycle priority (air conditioner)

    It is the function to set the location to detect humidity.
    You can use [<, > (left/right)] button to set the following setting values.

    This function can set cycle priority of outdoor unit.
    Multi V Heat Pump system does not support mixed mode therefore wired remote controller can
    not show opposite operation mode for select option while ODU operate cooling or heating cycle.
    Set this function user can select opposite operation mode with wired remote controller and indoor units enter to ‘standby’ status or outdoor unit can support cooling first and operate heating
    with heater.

    Value

    Description

    Remote controller (default value)

    Humidity sensor of the remote controller itself

    Indoor unit

    Humidity received from indoor unit

    OK

    ENGLISH

    Humidity sensing position (air conditioner)



  • Page 79

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 156

    156 INSTALLER SETTING

    INSTALLER SETTING 157

    Description

    Not use

    Does not support opposite cycle operation using wired remote controller
    - When ODU operate as cooling cycle selectable operation modes with
    wired remote controller are cool, auto, dehumidification and fan.
    - When ODU operate as heating cycle selectable operation modes with
    wired remote controller are heat, auto and fan

    Standby

    When user set opposite operation mode using wired remote controller indoor unit stop thermal operation and fan.

    Cool

    Cooling cycle has a priority.
    When user change operation mode of specific indoor unit to cooling on
    heating cycle, outdoor unit change cycle to cooling and Indoor unit keep
    heating operation using heater.
    h Please set emergency heater and aux heater function before using this
    option

    Outdoor temp. for heating stages (air conditioner)
    It is a function that sets outdoor temperature values for two stage heating.
    if user set outdoor temperature T1 and T2, Indoor unit will select heating stage between Indoor
    unit operation and heater operation.

    h When user select cooling option, additional setting menu will be activated.
    The additional timer setting menu is for setting minimum cooling operation period.
    Once outdoor unit change over to cooling by cooling priority, outdoor unit can change over to
    heating after set time.
    Setting value
    Step 0
    Step 1
    Step 2
    Step 3
    Step 4

    OK

    Cooling operation time
    45 min.(default)
    30 min.
    60 min.
    90 min.
    120 min.

    T1 Value

    T2 Value

    -23 ~ 16 °C (-10 ~ 60 °F)

    -23 ~ 51 °C (-10 ~ 130 °F)

    ENGLISH

    Option



  • Page 80

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 158

    158 INSTALLER SETTING

    INSTALLER SETTING 159

    Password initialization (air conditioner / general, DX ventilator)

    This function can set to display energy data which outdoor unit estimated power consumption
    data without wattmeter.

    It is the function to initialize (0000) when you forgot the password set in the remote controller.
    • In the installer setting list, select the password initialization setting category, and press [OK]
    button to move to the detail screen.
    • When you press “initialization” button, a popup screen appears, and when you press “check”
    button, password initialization starts, and the user password is changed to 0000.

    Setting value
    Use
    Not Use

    Description
    Display energy consumption data which outdoor unit estimated
    Not display energy consumption data which outdoor unit estimated

    CN_PTC setting (air conditioner)
    This is a function to set PTC Port of indoor unit.

    Setting value

    Description

    Normal

    Auxiliary heating interlock deactivated

    Special

    Auxiliary heating interlock activated

    OK

    ENGLISH

    Estimated energy display (air conditioner)



  • Page 81

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 160

    160 INSTALLER SETTING

    INSTALLER SETTING 161

    Express ventilation priority (general , DX ventilator)

    It is the function to set the direction of the ventilation product.
    • Select value using [<,>(left/right)] button.

    It is the function to set the priority of the air supply and air discharge during the express ventilation operation.
    • Select value using [<,>(left/right)] button.

    Value
    Normal

    Value

    Reverse
    Priority in air supply

    Priority in air discharge

    ENGLISH

    Product direction (general ventilator)



  • Page 82

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 162

    162 INSTALLER SETTING

    INSTALLER SETTING 163

    Humidification of ventilation with heating operation
    (DX ventilator)

    It is the function to set whether to use the humidification function during the ventilation product
    single operation.
    • Select value using [<,>(left/right)] button.

    It is the function to set the heating humidification function of the direct ventilation to be automatic or manual.
    • Select value using [<,>(left/right)] button.

    Value
    Not use

    Value
    Use

    Not use

    Use

    ENGLISH

    Humidification of stand-alone ventilation mode (general , DX
    ventilator)



  • Page 83

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 164

    164 INSTALLER SETTING

    GUIDE TO DIFFERENT MODE OPERATION/OPEN SOURCE SOFTWARE 165

    It is the function to change the standard fan speed of the ventilation product.
    • Select value using [<,>(left/right)] button.

    GUIDE TO DIFFERENT MODE
    OPERATION/OPEN SOURCE SOFTWARE
    Different mode operation
    Different mode operation is the case when the indoor units’ operation modes are different when
    multiple indoor units are installed to one outdoor unit. (Different mode operation doesn’t happen
    in the cooling exclusive model.)
    • Example of different mode operation
    - When one indoor unit is operated in heat while several indoor units one outdoor unit are operated in cooling, the heating operation is not performed.
    - With one outdoor unit, while several indoor units are in heat mode, if one indoor unit requests
    in cooling or dehumidification, the operation is not performed.

    Open Source Software Notice Information

    Value
    Default value

    10% increase

    10% decrease

    Filter check alarm(general ventilator)
    This function sets the filter check alarm of the ventilation product.
    • Select value using [<,>(left/right)] button.

    Value
    Step 0 - 5

    20% decrease

    To obtain the source code under GPL, LGPL, MPL, and other open source licenses, that is contained in this product, please visit http://opensource.lge.com. In addition to the source code, all
    referred license terms, warranty disclaimers and copyright notices are available for download. LG
    Electronics will also provide open source code to you on CD-ROM for a charge covering the cost
    of performing such distribution (such as the cost of media, shipping, and handling) upon email request to opensource@lge.com. This offer is valid for a period of three years after our last shipment of this product. This offer is valid to anyone in receipt of this information.

    ENGLISH

    Ventilation Fan Speed Alignment (general ventilator)



  • Page 84

    1,MFL69312302,영영 2018. 11. 19. 영영 11:19 Page 990






Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für LG PREMTBB10 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Holen Sie sich Ihr Benutzerhandbuch per E-Mail

Geben Sie Ihre E-Mail-Adresse ein, um das Handbuch zu erhalten von LG PREMTBB10 in der Sprache / Sprachen: Englisch als Anhang in Ihrer E-Mail.

Das Handbuch ist 16,03 mb groß.

 

Sie erhalten das Handbuch in Ihrer E-Mail innerhalb von Minuten. Wenn Sie keine E-Mail erhalten haben, haben Sie wahrscheinlich die falsche E-Mail-Adresse eingegeben oder Ihre Mailbox ist zu voll. Darüber hinaus kann es sein, dass Ihr ISP eine maximale Größe für E-Mails empfangen kann.

Andere Handbücher von LG PREMTBB10

LG PREMTBB10 Bedienungsanleitung - Deutsch - 84 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info