Specifications
Item
Model ESA30E-25
Power supply 3-phase 380V ±5% / 400V ±5% / 415V ±5% 50Hz
Operation to top up
(In intermediate season)
1
Heating capacity kW 30
Water amount Liter/min 8.97
Power consumption kW 6.98
COP 4.3
Operation to top up
(In cold region)
2
Heating capacity kW 30
Water amount Liter/min 5.06
Power consumption kW 10.73
COP 2.8
Operating sound
3
dB(A) 58
Outside dimension
Height mm 1,690
Width mm 1,350
Depth mm 720 + 35 (Water pipe connection)
Current
Max A 21
Starting A 5
Unit weight kg 375 (During operation 385)
Retained water amount L 10
Color Stucco white (4.2Y7.5/1.1 approx.)
Compressor
Type × Pcs Hermetic inverter compressor × 1
Nominal output kW 6.4
Refrigerant
Type R744 (CO2)
Charged amount kg 8.5
Refrigerant oil
Type MA68
Charged volume cc 1200
Crankcase heater W 20
Anti-freezing heater
for water pipe W 48 × 3
for drain pan W 40 × 2
for drain hose W 40 × 2 + 48
Heat exchanger, Air side Copper pipe straight fin type
Heat exchanger, Water side(Gas cooler) Copper pipe coil type
Fan
Type Axial flow type (direct coupled motor) × 2
Output × Pcs W 386 × 2
Air volume m
3
/min 260
Water pump
Type × output Non-self-suction spiral type inverter pump × 100W
Materials contacting to water Bronze, SCS13
Actual pump head m (kPa) 5m (49kPa) @17Liter/min
Usage temp range
Outdoor air temp °C –25 to +43
Feed water inlet temp °C 5-63
Hot water outlet temp °C 60-90
Water pressure range kPa 500 or lower
Defrost Hot gas type
Vibration and sound proofing devices
Compressor: placed on anti-vibration rubber and wrapped with sound insulation
Protection devices
High pressure switch, over current protection, power transistor overheat
protection and anomalous high pressure protection
Pipe size
Feed water inlet Rc3/4 (Copper 20A)
Hot water outlet Rc3/4 (Copper 20A)
Drain water outlet Rc3/4 (Copper 20A)
Electric wiring
Earth leakage breaker 30A, 30mA, 0.1sec
Power cable size
14 × 4 (Length 40m)
Moulded-case circuit breaker Rated corrent: 30A, switch capacity: 30A
Grounding wire size M6
Remote controller wire size 0.3mm
2
× 2cores shielding wire (MVVS)
Design pressure MPa High pressure: 14.0, Low pressure: 8.5
IP code IP24
(Note)
1. Performance of operation to top up in intermediate season shows the capacity measured under the conditions that outdoor air temp is 16°C
DB/12°C WB, water inlet temp is 17°C and hot water outlet temp is 65°C.
2. Performance of operation to top up in cold region shows the capacity measured under the conditions that outdoor air temp is –7°C DB/–8°C WB,
water inlet temp is 5°C and hot water outlet temp is 90°C excluding heater for anti-freezing water (345W).
3. Operating sound shows a value measured at 1m in front of the unit and 1m above the floor in anechoic room where the sound is resonated a little.
Accordingly if the unit is installed on actual site, it is normal that the measured sound there is higher than the value shown above, because it is
influenced by surrounding noise and echo in the room.
4. The actual hot water outlet temp may vary ±3°C from target temp according to the change of outdoor
air temp and water inlet temp. And then if feed water inlet temp is 30°C or higher and outdoor air temp
is 25°C or higher, hot water outlet temp may be controlled not to increase too high.
5. Please use the clean water. The water quality should follow a guideline of JRA-GL. 02:1994.
If the water quality is out of the standard, it may cause troubles such as scale buildup and/or corrosion.
6. These articles mentioned above may vary without any notice according to the development status.
Fixing heat pump unit
Anchor bolt M10 × 4
According to the installation conditions,
please take a measure to prevent from
falling, cross wind and heavy snow.
60

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Mitsubishi ESA30E series wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info