8.0 [N] Other adjustments
Menu 8.1.0 [N] Display settings
Settings concerning language and menu type are set in the sub-
menus to this menu.
Menu 8.1.1 [N] Menu type
The menu type is chosen here.
[N]
 
Normal, covers the normal users needs.
[U]
 
Extended, shows all menus except the service menus.
[S]
 
Service, shows all menus, returns to normal menu level
30 minutes after the last button was pressed.
NOTE
Incorrect settings in the service menus can damage the
property and/or heat pump.
Setting range: N, U, S
Menu 8.1.2 [N] Language
Language settings are made here.
Menu 8.1.3 [U] Display contrast
The display’s contrast is set here.
Setting range: 0 – 31
Menu 8.1.4 [U] Light intensity
The light intensity in idle mode is set here. Idle mode starts 30
minutes after the last button was pushed.
Setting range: 0=off, 1=low, 2=average.
Menu 8.1.5 [N] Return
Return to menu 8.1.0.
Menu 8.2.0 [N] Op. mode settings
Settings regarding auto mode can be made in the sub-menus to
this menu.
Menu 8.2.1 [N] Allow add. heat
You can choose at which operating mode the electric heater is
to be permitted to produce hot water and heat when needed.
Setting range: Off, Heating, Heating + Cooling, Cooling
Default values: Heating
Menu 8.2.2 [N] Add. heat mode
Selected if electric heater only is to be used to produce hot
water and heat.
Setting range: Off, On
Control
Menu 8.2.3 [U] Stop temp. heating
The average outdoor air temperature at which the heat pump (in
auto mode) is to stop heat production.
When the average outdoor air temperature falls below Stop
temp. heating – Hysteresis (menu 8.2.5) heating starts again.
Setting range: 1 – 43 °C
Menu 8.2.4 [U] Start temp. cooling
The average outdoor air temperature at which the heat pump (in
autoC mode) is to start cooling.
When the average outdoor temperature exceed it, cooling
starts.
When the average outdoor air temperature falls below Start
temp. cooling – Hysteresis (menu 8.2.5) cooling stops.
Setting range: 10 – 43* °C
* Operable temperature range is 15 – 43 °C.
Menu 8.2.5 [U] Hysteresis
See menu 8.2.3 and menu 8.2.4. Also affects control with room
sensor.
Setting range: 1.0 – 10.0
Menu 8.2.6 [N] Return
Return to menu 8.2.0.
Menu 8.3.0 [U] Current limiter
Settings and readings regarding the load monitor are set in the
sub-menus to this menu.
Menu 8.3.1 [U] Fuse size
The setting selected on the PCB (AA22) switch (R24) is shown
here.
Menu 8.3.2 [U] Max. electric power
The setting selected on the PCB (AA22) switch (R25) is shown
here.
Menu 8.3.3 [U] Current phase 1
Measured current from phase 1 shown here. If the value falls
below 2.8 A “low” is displayed.
Menu 8.3.4 [U] Current phase 2
Measured current from phase 2 shown here. If the value falls
below 2.8 A “low” is displayed.
Menu 8.3.5 [U] Current phase 3
Measured current from phase 3 shown here. If the value falls
below 2.8 A “low” is displayed.
Menu 8.3.6 [U] Transform. ratio EBV
The transfer value must be defined depending on the current
transformers used for the PCB.
Setting range: 100 – 1250
34

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Mitsubishi HMA100V wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.