Fig. 21 N - V controller, boiler with 7 and 9 sections
Fig. 22 N - V controller, boiler with 11 to 19 sections
16. Switch the boiler to full load by selecting option
"Load maximum" with the ' ' button and confirming it
with the ' ' button.
Compare the CO
2
percentage with the value men
tioned in the table. Adjust, if necessary, this CO
2
percentage with the V-controller. Switch the boiler to
part load, measure and compare the CO
2
percentage
with the value mentioned in the table and adjust, if
necessary, the value with the N-controller.
17. Repeat this full load/part load switching until the CO
2
percentages at full load/part load come within the
tolerances mentioned in the table.
18. By pressing the ' ' button, the main menu of the
service level reappears. Now set the desired boiler
control, as described in para. 7.3.3.
By pressing the ' ' button three times, you return to
the main menu of the user level.
19. After commissioning, enter the preset values in the
table on the boiler.
20. Send the CE commissioning report to Broag.
11.3 Shut down the boiler
1. Turn off the power supply to the boiler.
2. Close the main gas cock.
3. Turn off the boiler control.
Please note! Frost protection may be required.
12. FAULT-FINDING
- Now select the option “History data” with the ' ' button
and confirm it with the ' ' button.
- Now select the lock out or shut down failure memory
using the ' ' button. Confirm with the ' ' button.
Depending on the option selected, the number of
locking failures stored in the memory (maximum 5 of
each) is now displayed.
Failure No. 1 is the failure which occurred last, failure
No. 2 the last but one, etc.
To know which failure occurred last, the failure counter
must be set to 1 using the ' ' and ' ' buttons. When the
' ' button is pressed for confirmation, the failure in
question is indicated. Using the ' ' button, various
menus can now be called up, all indicating the opera-
tional condition of the boiler at the moment of failure.
In the table below the various failure messages are dis-
played which may appear on the LCD-display, followed by
the instructions to eliminate the failure.
For possible measurement methods see chapter 11:
"Commissioning". When a failure message appears that
is not selfexplanitory, and is not displayed in the table,
then contact our service department.
Note:
When reporting a failure code, write down the exact mes-
sage and the parameters at which the failure occured.
12.1 General
For troubleshooting use the wiring diagram and the swit-
ching sequence diagram in paragraph 10.9. The instru-
ment panel is provided with an alphanumeric LCD-display.
In the case of failure, the display indicates the cause of
the failure and how long ago the boiler went into failure
mode. The failure and the operating condition at the time
of failure are stored in the memory of the control unit.
Five blocking and five locking failures can be stored in
this memory. If a failure in a boiler repeats itself several
times in rapid succession, this failure is stored only once.
Locking failures can be reset using the reset button on
the instrument panel (' ').
12.2 Faults
In the case of failure, the LCD-display indicates the cause
of the failure. It also indicates whether it is a blocking or
locking failure and how long ago it occurred. In the case
of a blocking failure, the boiler will automatically restart
when the cause of the failure has been eliminated. If the
same blocking failure has occurred 5 times in rapid suc-
cession, the boiler will lock out. Displaying the operational
condition at the time when the failure occurred speeds up
the search for the cause of failure.
Proceed as follows:
- Select the service level by travelling down the user
menus using the ' ' button. Enter code 00 12 using the
'' and ' ' buttons and confirm it with the ' ' button.
31

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Remeha Gas 3002 ECO wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Remeha Gas 3002 ECO

Remeha Gas 3002 ECO Bedienungsanleitung - Deutsch - 28 seiten

Remeha Gas 3002 ECO Bedienungsanleitung - Holländisch - 2 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info