735232
2
Zoom out
Zoom in
Vorherige Seite
1/2
Nächste Seite
Product Compliance & Safety Information
Product Compliance
SALUS Controls hereby declares that the product complies with the essential
requirements of the following EC Directives: 2014/30/EU, 2014/35/EU and
2011/65/EU. The full text of the EU Declaration of Conformity is available at the
following internet address: www.saluslegal.com.
Safety Information
Use in compliance with safety regulations. The unit is to be used for the control of
room temperature inside the house.
Installation
This accessory must be fitted by a competent person, and installation must
comply with the guidance, standards and regulations applicable to the city,
country or state where the product is installed. Failure to comply with the relevant
standards could lead to prosecution.
Note: All electrical installation work should be carried out by
a suitable qualified electrician or other competent person.
Product Description
Thank you for purchasing the SALUS HTR230 Thermostat. This thermostat is a
device that lets you customise the heating and cooling of your home as needed.
The HTR230 is an electronic room temperature controller which offers key
advantages over conventional mechanical products.
The controller is easy to operate using the conventional backlit adjusting dial
and offers you unique control convenience for heating applications of all types
thanks to the high quality device electronics.
We hope you enjoy our product.
Contents of the box
Manual Contents:
Box Contents
Introduction
Product Compliance and
Safety Information
Installation
User Interface
Status/LED indication
Installers notes
Warranty
Icons used in this manual:
Safety
Important info
Your benefit
Fixing Screws
1 x Installer Manual
Dial Thermostat
Model: HTR230
INSTALLER MANUAL
SALUS Controls plc
SALUS House
Dodworth Business Park South,
Whinby Road,
Dodworth, Barnsley S75 3SP, UK.
Sales: T: +44 (0) 1226 323961
E: sales@salus-tech.com
Technical: T: +44 (0) 1226 323961
E: tech@salus-tech.com
www.salus-controls.com
SALUS Controls is a member of the Computime Group
Maintaining a policy of continuous product development SALUS Controls plc reserve the right to
change specification, design and materials of products listed in this brochure without prior notice.
Issue Date: Dec 2015
00086/2
For PDF Installation guide please
go to www.salus-manuals.com
8. Technical Specification
Model: HTR230
Voltage:
230 V AC, +-10%, 50/60 Hz
Operating Performance:
230 V: 1,8 W
Temperature setback:
Temperature range:
2°C-4°C
5°C- 30°C
Span:
+/- 0,5°C
Calibration:
Yes, with jumper
Storage temperature:
-20°C to +60°C
Ambient temperature:
0 °C up to 45 °C
Degree of protection:
IP 30
CE conformity according to:
Class II ( EN60730 )
Housing material:
PC, V2
Color:
RAL 9010 pure white
Connection:
Screw terminal
Weight
90g net / 135g gross
Puls-wide-modulation:
(PWM)
Yes
Valve protection:
Heating and Cooling:
Cooling blocked:
Dimensions:
Yes
Yes, automatically Change Over on the CO terminal
Yes, with jumper
85mm*85mm*25mm
Warranty
SALUS Controls warrants that this product (HTR230) will be free from any
defect in materials or workmanship, and shall perform in accordance with
its specification, for a period of five years from the date of installation.
SALUS Controls sole liability for breach of this warranty will be (at its option) to repair
or replace the defective product.
Customer Name: ......................................................................................................................................................
Customer Address: .................................................................................................................................................
............................................................................................................................................................................................
....................................................................................... Post Code: ...........................................................................
Tel No: .................................................................... Email: .......................................................................................
Engineers Company: ..........................................................................................................................................
Tel No: ...................................................................... Email: ....................................................................................
Instalation Date: ....................................................................................................................................................
Engineers Name: ...................................................................................................................................................
Engineers Signature: ...........................................................................................................................................
6. Protection Function
7. Control Patterns
5. Thermostat Functions
NSB (Night SetBack) Function
NSB Mode depends on the NSB wired connection.
0V = NSB OFF
24V= NSB ON
The NSB signal is activated every 1 second. When the signal is received the
setpoint temperature will be set at ±2°C or ±4°C.
Heating and Cooling Selection
The Heating/Cooling function is determined by the CO terminal connection.
CO 0 V= Heat mode
CO 24V= Cool mode
Cooling Blocked function
Cooling Enabled:
Set the jumper on ON . The thermostat will run in normal cooling mode.
That means that it will open/close the actuators when necessary. The LED will be
BLUE when the cooling function is running.
Cooling Disabled:
Set the jumper on OFF . The actuator will be closed and the LED will
be off.
Heat cut o at high/low temperature:
When room temperature is over 36°C or under 4°C, all heating/cooling outputs
will be turned off.
Short cycle protection:
When Cooling Mode is enabled the minimum interval between Relay ON/OFF
is 3 minutes.
Valve Protection:
Set the jumper on ON to disable the function or on OFF to enable it. Turn on the
valve for 5 minutes every week to prevent the valve any damages on the valve.
Sensor Malfunction:
If the temperature sensor or temperature sensor compensation is open the LED
will flash BLUE/RED alternatively.
If CO terminal is connected and the Heating Mode is ON, the PWM function
will be activated.
If CO terminal is disconnected and the Cooling Mode is ON the ON/OFF control
output will be activated.
HTR230 Thermostat
Gently remove front housing and
make the wiring connections.
2. Terminal Connection 4. Jumpers
1. Mounting the Thermostat 3. Switching Bridges
Note: You can wire the thermostat
directly to the KL08NSB Wiring
Center (purchased separately).
Wall mounting
For wall mounting, mark the correct
possition on the wall and mount the
rear case to the wall.
Install the HTR230 dial room thermostat at roughly 1.5m above floor level. It
should be mounted in a location where the thermostat is easily accessible and
away from direct sunlight.
CO
N
L
ACTUATOR
30ºC
25
N
L
E.G.
HEAT
PUMP
EXTERNAL
CLOCK
230VAC
50Hz
CO
N
L
30ºC
25
Different features of the HTR230
can be switched On or OFF with
the jumpers. In order to do this
please follow the table below.
HTR 230 Switching Bridges
Switch
VP Valve protection feature
Pulse-Width-Modulation
NSB Function (2° or 4°)
Heating/Cooling
PWM
CO
Feature
ON
OFF
2°C
Enable Disable
4°C
The jumpers from 1 to 5 are representing the number of actuators that you can connect
to the thermostat.
After the actuators are mounted please move the jumper on the correct number (the
same as the number of actuators).
Depending on the amount of actuator used, please change the jumper position
accordingly to compensate the power consumption.
2

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Salus HTR 230V wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Salus HTR 230V

Salus HTR 230V Bedienungsanleitung - Deutsch - 2 seiten

Salus HTR 230V Bedienungsanleitung - Holländisch - 2 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info