2 CE1G2406E
3. Functional check
1. DO NOT switch on power yet!
2. With wall mounting: separate controller from the
base.
With flush panel mounting: separate terminal strips
from the controller.
3. Check wiring to make certain it is in compliance
with the plant wiring diagram.
4. Fit controller or terminal strips, depending on the
method of installation.
5. Check the regulating unit: Seat or slipper valve:
Ensure it is correctly fitted (observe direction of
flow indicated on the valve body)
Make certain the slipper operates in the correct
range (note position indicator)
Ensure the manual adjuster is disengaged
6. Note with underfloor and ceiling heating systems:
the limit thermostat must be correctly set. During
the functional check, the flow temperature must not
exceed the max. permissible level (usually 55 °C).
If that is the case, proceed immediately as follows:
Close the seat or slipper valve manually
Switch off the pump
Close the pump isolating valve
7. Switch on power.
The display must show something (e.g. the time of
day). If that is not the case, the cause is probably
one of the following:
No power
Main fuse blown
Manual switch not in position ΙΙ
3.1 Detector test
The detector test or the display of the actual tempera-
ture is activated by pressing the TEMP button. Press
TEMP several times. First, the 5 adjusted set value
temperatures appear, then the 8 following temp.:
Display Detector VG1-
VG6
VG0
TEMP 1 D.h.w. temperature detector 1 /
Primary return temp. detector 2
Remote telephone switch
B31 B11
TEMP 2 D.h.w. temperature detector 2
Secondary return temp. detector 2
B3 B3
TEMP 3 Primary return temperature detector B7 B7
TEMP 4 Secondary return temperature detec-
tor / D.h.w. charging detector
B71 B71
TEMP 5 Secondary flow temp. detector B1 B1
TEMP 6 Flow temp. detector heating circuit
Flow temp. detector d.h.w. circuit
Primary return temp. detector 2
B11 B11
TEMP 7 Outside detector B9 B9
TEMP
8 Room temperature detector A6 A6
Check:
If, in case of display of an actual temperature, o o o
appears in place of the temperature, the respective
detector has a short-circuit.
If, in case of display of an actual temperature, - - - ap-
pears in place of the temperature, the respective de-
tector is not connected.
The detector test mode can be quit either immediately
by pressing one of the operating mode buttons, or
automatically after about eight minutes.
3.2 Relay test
Button
Display Relay Effect
0
+
Relay test mode
active
1
+
Q1 Heating circuit
pump 1 on
2
+
Q3 /
Y3
D.h.w. charging
pump on
3
+
Q4 Storage tank
charging pump
on
4
+
Q5 D.h.w. circulating
pump on
5
+ 5:XX
5:XX
5:XX
Y1
Y2 Control valve
opens
Control valve
closes
6
+ 6
6
6
Y11
Y22
Valve opening
Valve closing
The relay test mode can be quit immediately by
pressing any of the operating mode buttons, or auto-
matically after about eight minutes.
Note:
Test step 5
XX = valve position according to stroke model (in %)
Terminal Y4 is always under voltage when Q3/Y3 is
deenergized!
4. Enduser settings
These are settings that can be made to meet individual
needs. They are directly accessible from the user inter-
face. For procedure, please refer to the operating in-
structions supplied with each controller.
5. Installer settings
These are plant-related settings that should only be
changed by the heating installer. They are subdivided
into different groups that can only be selected by
pressing combinations of buttons (please refer to the
table below).
The display shows the selected group, the parameter
and the adjusted value.
Combination of
buttons
Function
1
+
Selecting group C, F or H
2
+
5 Sek.
Selecting group U
Note: first, select button combination 1
3
+
+
Selecting the parameters of the group
Note: forward and reverse selection
possible
4
Adjusting the values
The parameter setting level can be quit either imme-
diately by pressing one of the operating mode buttons,
or automatically after about eight minutes.
Factory-set parameters:
Plant diagram VG1
2

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln
1

Forum

siemens-sigmagyr-rvp97

Suche zurücksetzen

  • Benötige die Kurzanleitung und die ausführliche Bedienungsanleitung der Regelung Landis & Gyr, RVP 96770, in deutscher Sprache. Bitte helfen Sie mir. Freue mich auch allenfalls um Übermittlung per Mail an gv.lohninger@aon.at.
    Vielen Dank
    Franz Lohninger
    Weinbergweg 33
    4880 St. Georgen im Attergau Eingereicht am 26-9-2022 08:45

    Antworten Frage melden
  • Hallo,
    Ich brauche eine deutsche Anleitung für die SIGMAGYR RVP97.
    Finde ich die vielleicht an anderer Stelle im Internet?
    Oder kann mir jemand eine über meine E-mail zukommen lassen?
    mit besten Grüßen
    Wendelin Schliehe-Diecks
    (wendelinsd@web.de)

    Eingereicht am 1-11-2019 13:49

    Antworten Frage melden

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Siemens SIGMAGYR RVP97 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info