FAN-COIL 4T
Electronic Controller
Fig. 1
Fig 2.
Fig.3
Fig.4
Fig 5.
Safety warnings and operating instructions
• This product should be installed preferably by a qualified professional. Subject to observation of the
above terms, the manufacturer shall assume the liability for the equipment as provided by legal
stipulations. All instructions in this
Installation & Operation manual should be observed when working with the controller.
• Failures due to improper installation, improper use or poor maintenance are voiding manufacturer
liability
• Any attempt to repair voids the responsibility and the obligation to guarantee and replacement from
the manufacturer.
Product description:
FAN-COIL CONTROLLER 4T: Fan-coils electronic controller suitable for models equipped with
double heat exchanger (4-pipes plants), 3-speeds asynchronous electric motor connected to the fan,
ON/OFF type valves, SUMMER/WINTER switch either manual or automatic (on the basis of the air
temperature), ventilation consent on the basis of the water temperature (if necessary).
Operating instructions and legend (Fig.1):
Two steps ON/OFF button
OFF mode
ON mode with manual ventilation
Manual ventilation switch (minimum, middle, maximum speed)
Blue and red warning
Led is permanently blue: fan coil is in cooling mode
Led is permanently red: fan coil is in heating mode
Red led is blinking: water temperature is too low to heat
Both red and blue led blinking: temperature probe is faulty or disconnected
Control knob for temperature setting from 5 to 35 °C
Manual switch mode
SUMMER/COOLING
WINTER/HEATING
Wall mounting instructions:
Install the controller in an easily accessible area suitable for functions setting and efficient for room
temperature detection (at least 1.5 m from the floor). Therefore, avoid:
direct sunlight exposure
direct exposure to hot or cold air currents
placing obstacles which impair correct temperature detection (curtains or furniture);
the constant presence of water vapour (kitchens, etc.)
covering or recessing the controller into the wall.
Please, respect the following instructions (Fig.2)
remove the controller temperature setting knob
• remove the controller closing screw
pass the cables through the slots on the base and fasten the controller with the reserved holes
close the controller back up using the closing screw and insert again the temperature setting knob
Electrical connections:
All of the operations must be carried out by qualified staff, in accordance with regulations in force.
For any electrical related procedure, refer to the electrical diagrams attached to this documentation.
We also suggest making sure that the characteristics of the electrical network are suitable for the
absorption levels reported in the electrical data table. Before carrying out any operation on electrical
parts, make sure the power supply is disconnected. Check that the net voltage is compatible with the
specifications of the unit (voltage, number of phases, frequency) shown on the unit rating plate. The
supply voltage must not fluctuate by more than ±5% in relation to the rated value. The electrical
connections must be set up according to the electrical diagram attached to the specific unit and with
the regulations in force.
Operating and adjustment setting
On the electric circuit of the controller there are electric devices able to modify three different settings:
REMOTE jumper used to specify the position of the air probe on the basis of which the
controller makes the adjustment. The two possibilities are on board probe (factory default
setting) or remote wired probe (Fig. 3).
• AUTO jumper to specify how the changeover (SUMMER/WINTER) is supposed to be applied
by the controller). The two possibilities are the manual selection (factory default setting) or the
automatic changeover on the basis of air temperature (Fig. 3).
Potentiometer for the hysteresis calibration (from 1°C to 10°C) around the temperature SET
for the automatic SUMMER/WINTER changeover, we suggest not to modify this value if not
strictly necessary, for example as a consequence of a quick and large variation of the air
temperature (Fig. 3)
Adjustment logics:
The thermostat operation (either cooling or heating) takes place with a difference of 0,2°C from the
set point of the controller (Fig. 4). The thermostat switches on the fan and opens the valve (if any).
Ventilation is activated (limited to 2 minutes every 8 minutes) and forced without a real necessity only
with the following setting: cooling mode and remote air probe; this is due to the fact that in this
situation a good air temperature detection is possible only if the air is periodically moved.
The water consent to ventilation (only if the water probe is connected) is driven by the activation and
deactivation logic reported in figure 5.
Technical data:
Power supply
230 V - 50/60Hz
IP rating
IP30
Exit relay
6(2)A/250V
Temperature probes
NTC 10K Ohm @25°C
Electric class of protection WAT FAN
COIL CONTROLER 2T and 4T
II
Dimensions
125 x 75 x 32 mm
EU Declaration of conformity
Hereby, Watts Electronics declares
that the equipment is in compliance
with the relevant Community
harmonisation legislation:
•Directive 2001/95/EC on
General Products Safety
• Low Voltage Directive
2014/35/EU
RoHS Directive 2015/863
Weight
0.162kg
The full text of the EU declaration of conformity is available by written request to https://wattswater.eu
Wiring diagram
1
Neutral
7
Neutral fan speed
2
Live
8
Neutral heating actuator
3
Heating/cooling actuator.
9
Neutral cooling actuator
4
Minimum fan speed
10 -11
Water probe (Option)
5
Medium fan speed
12- 13
Air probe (Option)
6
Maximum fan speed
C1
Two steps ON/OFF button
C2
Manual ventilation switch
C5
Control knob for temperature
setting
Displosal and recycling information:
2012/19/EU (WEEE directive): Products marked with this symbol cannot be disposed of
as unsorted municipal waste in the European Union. For proper recycling, return this
product to your local supplier upon the purchase of equivalent new equipment, or dispose
of it at designated collection points. For more information see: www.recyclethis.info
Contact us
Watts Electronics S.A.S
B.P. N°10 - Z.A. des Tourettes
43800 ROSIERES, France,
T: +33 4 71 57 40 49, F: +33 4 71 57 40 90
https://wattswater.eu
GB
1

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Watts FAN -COIL 4 T Electronic Controller wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info