The JA-80Y GSM communicator - 10 - MFJ55304
zz..z installation ID number, max. 8 characters (0 to 9 and
1=A to 6=F - hexadecimal number)
Factory default setting: 0000 for both ARCs
5.26. Selecting the ARC communication protocol
To select the required communication protocol enter:
04 a x
where:
a 1=ARC1, 2=ARC2
x 0=Contact ID, 1=SMS CID, 2=IP CID
Notes:
IP CID is the fastest of the above protocols and it also allows very
frequent checking of communication reliability with the ARC (e.g.
every 5 minutes)
Contact ID protocol can be used with ARCs linked by standard
telephone lines (if they support Contact ID)
If your ARC does not allow SMS CID or IP CID protocols, please
contact a Jablotron distributor for details on how to update your
ARC.
Factory default setting: Contact ID for both ARCs
5.27. Selection of events to report to ARCs
The system recognizes 32 different types of events - see the following
table. This sequence allows you to select which events are reported to
which ARC.
05 a ec x
where a 1 = ARC1, 2 = ARC2
ec event code 01 to 32
x 0 = no report, 1 = report
Factory default setting: all events are reported
ec Event
01 Intruder alarm - instant
02 Intruder alarm - delayed
03 Fire alarm
04 Panic alarm
05 Number of permitted incorrect code-entries
exceeded
06 Alarm triggered during control panel power-up
07 Tamper alarm
08 End of tamper alarm
09 End of alarm indication
10 Alarm cancelled by user
11 Setting
12 Unsetting
13 Partial setting
14 Codeless setting
15 External communication fault
16 External communication restored
17 Fault
18 Fault no longer present
19 Mains dropout longer than 30 minutes
20 Mains dropout
21 Mains restored
22 Discharged battery
23 Battery OK
24 Switching to Service Mode
25 Leaving Service Mode
26 PGX ON/OFF
27 PGY ON/OFF
28 Radio communication jamming present
29 Internal communication fault
30 Internal communication restored
31 Communication test
32 Unconfirmed alarm
Besides the events listed above, the communicator also reports some
events which are not selectable here (e.g. the annual inspection
request if enabled in the control panel = CID 1393)
5.28. Defining the delay before data is resent to an ARC
The communicator tries to send reports to the main number / IP
address, and if unsuccessful it then tries the backup number / IP
address. If still unsuccessful, it then tries to re-send the data to both
the ARCs again as before, but after a period defined by:
06 a x
where
a 1 = ARC1, 2 = ARC2
t is the period: 0=immediately, 1 to 9 = 1 to 9 minutes
Factory default setting: 1 min. for both ARCs
5.29. ARC communication checking period
The time to wait after the last report sent to an ARC before performing
an ARC communication check is set by this sequence. The
communication-checking event code is 31 (see 5.27). This sequence
programs how often the communication check is performed:
07 a hhmm
where
a 1 = ARC1, 2 = ARC2
hh hours
mm minutes
Notes:
Checking reports are not sent in service mode
IP CID protocol allows very frequent checking of ARC
communication (e.g. every 5 minutes).
Factory default setting:24 hours after the last report – for both ARCs
5.30. Enable ARC reporting (ARC2 backs up ARC1)
This sequence allows reporting to ARCs to be switched on/off and also
enables ARC2 to backup ARC1:
00 a x
where
a 1=ARC1, 2=ARC2
x 0=off, 1=on, 2= ARC2 backs up ARC1 (2 can only be
entered for ARC2)
Note: if ARC2 backs up ARC1 then it will only receive data if it is not
possible to deliver it to ARC1. A report containing “Communication
fault to ARC1” is then sent to ARC2 together with the first report to
ARC2.
Factory default setting: both ARCs = off
5.31. Recording reports sent to ARCs in the control panel
memory
This sequence enables the recording of every report successfully
communicated to ARCs in the control panel’s internal memory.
080 enabled
081 disabled
Note: it is recommended not to record reports sent to ARCs but to
enable the indication of ARC communication faults (see 5.32). This
saves a significant amount of control panel memory. The system
initially assumes that every report is successfully delivered to ARCs,
but if a report is not successfully delivered within 110 seconds of
transmission, then a communication fault will be indicated and
recorded.
Factory default setting: enabled
5.32. Indicate an ARC communication fault if a report is not
successfully received within 110 sec of transmission
Enables the indication and recording of a communication fault if a
report is not successfully delivered to an ARC within 110 seconds of its
transmission.
090 communication faults not indicated
091 communication faults indicated
Notes:
The communicator continues trying to send information to an ARC
even after a communication fault has been indicated (after the data
has been delivered, communication fault indication stops).
For communication-checking reports the delivery time limit
(confirmation from the ARC) is 300 minutes. But if any other report is
sent to the ARC it must be confirmed within 110 seconds (otherwise
a communication fault will be indicated)
Factory default setting: communication faults not indicated
10

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Jablotron JA-80Y wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Jablotron JA-80Y

Jablotron JA-80Y Bedienungsanleitung - Englisch - 16 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info