Digital communicator JA-65X 4/7 MFM53102
The Surgard protocol has 4/2 structure plus one more digit
which is generated automatically (see 4.3)
If the control panel is split and only one section is armed,
then a partial arming report code is sent. If all sections are
armed, a complete arming report code is sent. If the
system was completely armed and only one section is
disarmed, the disarming report code will be sent and then
it will be followed by the partial arming report code.
The pulse formats are not capable to report zero and
numbers above 15. For this reason events in zone 16 or in
a subsystem are reported to the Monitoring Station as
events in zone 10. This means that from the point of view
of the monitoring station zone 10 also covers zone 16 and
the subsystem if used. This problem does not exist in the
CID protocol.
If the system is arming while there is a bypass, partial
arming will be reported to the CMS (also stored to the
internal memory)
Factory setting: 00 for all events
4.2 Account ID code setting
sequence: 02
This sequence is used for the alarm system identification by a
Monitoring Station. The sequence structure: 02 x x x x
where:
xxxx – account ID code ( x are numbers from 0 to 9 or
hexadecimals).
When using only three-digit codes (formats 3/1 and 3/2) enter
a zero in the first position. The communicator will then ignore it
(example - 0123)
Note: Changing of the account code erases the internal
communicator’s memory of non reported events and sends a
„Reset“ reporting code (051) to the Monitoring Station. If pulse
formats are used, zero is transmitted as A
h
Factory setting: 0000
4.3 Protocol and Format setting
sequence: 03
This sequence is used to select the communication protocol
and format. Its structure is as follows: 03 x y
where:
x - protocol (0 – 9, see table bellow)
y - format (0 - 3 see table on right)
Notes:
Some Monitoring Station receivers do not support all formats.
Logic of the format marking - 4/2 means that an account code has
4 digits and an event report code has 2 digits.
Changing of a format erases the internal communicator’s memory
of non reported events and sends a “Reset“ reporting code (051)
to the Monitoring Station.
Factory setting: 90 (Contact ID)
4.4 Re-dialing pause setting
sequence: 04
If a dialer is triggered it attempts to make a connection
(alternating between the primary and the backup telephone
number). If it is not possible to make a connection after 8
attempts, a pause is initiated. After this pause the dialer will
attempt again. If any event triggers the communicator during the
pause, the pause ends immediately. The pause length can be set
in the following way:
0 4 x
where:
x – time multiplied by 10 minutes (from 1 to 9, example 3 =
30 minutes)
Factory setting: 1 = 10 min.
4.5 CMS phone number entering
sequence: 06
Central monitoring station modem phone numbers can be
stored by entering the following sequence: 0 6 x x .... x F y
where:
xx...x = Central Monitoring Station phone number (up to
16 digits)
y = 1 for primary phone number memory
2 for back up phone number memory
Pause (3 sec.) can be inserted into the telephone number by
entering F0. It is also possible to insert the * tone by F7 or the
# tone by F8 if requested for DTMF dialing.
Example: number 02 123456 as main Monitoring Station
number is entered with 06 02 F0 123456 F1.
Phone number erasing: 0 6 F 0 F y
where:
y = 1 to erase the primary telephone number
2 to erase the back up telephone number
Protocols
x Name
Hand-
shake
Data Kiss off Speed
format
0
Ademco Slow
(Silent Knight)
1400Hz 1900Hz 1400Hz 10bps
Next
table
1
Ademco Fast 1400Hz 1900Hz 1400Hz 14bps
Next
table
2
Telemax 2100Hz 1650Hz 2100Hz 10bps
Next
table
3
Franklin 2300Hz 1800Hz 2300Hz 20bps
Next
table
4
Radionics 2300 2300Hz 1800Hz 2300Hz 40bps
Next
table
5
Radionics 1400 1400Hz 1900Hz 1400Hz 40bps
Next
table
6
DTMF 2300 2300Hz DTMF 2300Hz DTMF
Next
table
7
Surgard* 2300Hz DTMF 2300Hz DTMF
4/3
8
Ademco express* Dual tone DTMF 1400Hz DTMF
4ID/2
9
Contact ID* Dual tone DTMF 1400Hz DTMF
CID
* fixed format, “y” is arbitrary (0 is recommended)
Formats
y
format reports structure
0
3/1
Major events only
xxx R
1
3/2
All events
xxx rc
2
4/1/1
Major events with autom. source
identification
xxxx Rn
3
4/2
All events
xxxx rc
xxxx = account number
R = major event code (only first digit counts)
rc = detailed event code (two digits)
n = source identification (generated automatically)
Surgard protocol has structure: xxxx E rc, where E is a group
identifier (generated automatically)
E Event Note
1 Fire
2 Panic
3 Alarm General
4 Arming Incl. Partial
5 Disarming
6 Failure Power failure, RF jamming …
8 Report Enter/Exit service mode …
9 Restore End of alarm, panic …
A Test 24 hour test
4

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Jablotron JA-65X wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info